2018-11-20 13:08:21THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) SHEET LS 1 - AN EXIT SIGN IS INDICATED WITHIN A
 CLOUD IN THE ACCOUNTING ROMM LEADING INTO THE STORAGE
 AREA. THIS EXIT IS NOT REQUIRED, ADDITIONALLY, AN EXIT
 FROM AN AREA OF LOWER HAZARD CAN NTO EXIT INTO AN AREA
 OF HIGHER HAZARD.
  
 PLEAE OMIT THIS EXIT SIGN.
  
 7.5.1.6 EXIT ACCESS FROM ROOMS OR SPACES SHALL BE
 PERMITTED TO BE THROUGH ADJOINING OR INTERVENING ROOMS
 OR AREAS, PROVIDED THAT SUCH ROOMS OR AREAS ARE
 ACCESSORY TO THE AREA SERVED. FOYERS, LOBBIES, AND
 RECEPTION ROOMS CONSTRUCTED AS REQUIRED FOR CORRIDORS
 SHALL NOT BE CONSTRUED AS INTERVENING ROOMS. EXIT
 ACCESS SHALL BE ARRANGED SO THAT IT IS NOT NECESSARY TO
 PASS THROUGH ANY AREA IDENTIFIED UNDER PROTECTION FROM
 HAZARDS IN CHAPTERS 11 THROUGH 43.
  
  
  