| 2018-10-10 17:45:53 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18081507 |
| | 10/10/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) NO MECHANICAL PLANS WERE SUBMITTED FOR THIS |
| | ALTERATION PROJECT EXCEPT A NOTE AND A DETAIL ON SHEET |
| | EP-1 ADDRESSING THE RELOCATION OF AN AHU AND HOW IT |
| | WILL BE SUPPORTED ABOVE THE CEILING. PLEASE PROVIDE THE |
| | FOLLOWING: |
| | |
| | A) PROVIDE THE LEVEL OF ALTERATION FOR THE PROPOSED |
| | PROJECT- SEE CHAPTER 5 FBC EX AMD DETERMINE IF THE |
| | PROJECT IS A LEVEL 1, 2, OR 3 ALTERATION OR A CHANGE OF |
| | OCCUPANCY. |
| | |
| | B) MINIMUM VENTILATION RATES FOR ALL ROOMS AND SPACES: |
| | REFER TO SECTION 809.2 FBC-17 EXISTING BUILDING CODE |
| | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL |
| | ROOMS AND SPACES PER TABLE 403.3.1 FBC-17 MECHANICAL. |
| | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND |
| | PROVIDED CFMS OF OUTDOOR AIR. |
| | |
| | C) EXHAUST VENTILATION CALCULATIONS FOR THE DISPATCH |
| | AND LOADING AREAS. PLEASE REVIEW SECTION 406 AND |
| | IDENTIFY IF THE AREAS IN QUESTION ARE TO BE CLASSIFIED |
| | AS PRIVATE OR PUBLIC GARAGES. IN EITHER CASE EXHAUST |
| | VENTILATION SYSTEMS SIZED AT A RATE OF 0.75 CFMS PER |
| | SF. WILL BE REQUIRED- TABLE 403.3.1.1 FBC M. |
| | |
| | D) PROVIDE A DUCT LAYOUT PLAN SHOWING THE REQUIRED |
| | ALTERATIONS TO THE EXISTING SYSTEMS TO ACCOMODATE THE |
| | NEW ROOMS AND SPACES WITH BALANCED AIR CONDITIONING- |
| | SECTION 603.1 FBC M. |
| | |
| | E) PROVIDE AN AIR DEVICE SCHEDULE. |
| | |
| | F) SHOW HOW THE WAREHOUSE IS BEING VENTILATED AND WHAT |
| | MATERIALS ARE BEING STORED THERE- SEE SECTIONS 401.2, |
| | 402.1 AND TABLE 403.3.1.1. |
| | |
| | G) CLARIFY THE USE OF THE CHARGING STATION SHOWN IN THE |
| | WAREHOUSE OF SHEET EP-1. PLEASE NOTE THAT AN EXHAUST |
| | VENTILATION SYSTEM IS REQUIRED FOR BATTERY CHARGING |
| | AREAS PER SECTIONS 502.3- 502.5.3 FBC M. |
| | |
| | |
| | PLEASE NOTE THAT DUE TO THE LACK OF MECHANICAL PLANS |
| | THERE MAY BE ADDITIONAL COMMENTS WHEN COMPLETE PLANS |
| | AND CALCULATIONS ARE SUBMITTED. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |