Plan Review Notes
Plan Review Notes For Permit 18081507
Permit Number 18081507
Review Stop M
Sequence Number 1
Notes
Date Text
2018-10-10 17:45:531ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18081507
 10/10/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) NO MECHANICAL PLANS WERE SUBMITTED FOR THIS
 ALTERATION PROJECT EXCEPT A NOTE AND A DETAIL ON SHEET
 EP-1 ADDRESSING THE RELOCATION OF AN AHU AND HOW IT
 WILL BE SUPPORTED ABOVE THE CEILING. PLEASE PROVIDE THE
 FOLLOWING:
  
 A) PROVIDE THE LEVEL OF ALTERATION FOR THE PROPOSED
 PROJECT- SEE CHAPTER 5 FBC EX AMD DETERMINE IF THE
 PROJECT IS A LEVEL 1, 2, OR 3 ALTERATION OR A CHANGE OF
 OCCUPANCY.
  
 B) MINIMUM VENTILATION RATES FOR ALL ROOMS AND SPACES:
 REFER TO SECTION 809.2 FBC-17 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3.1 FBC-17 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 C) EXHAUST VENTILATION CALCULATIONS FOR THE DISPATCH
 AND LOADING AREAS. PLEASE REVIEW SECTION 406 AND
 IDENTIFY IF THE AREAS IN QUESTION ARE TO BE CLASSIFIED
 AS PRIVATE OR PUBLIC GARAGES. IN EITHER CASE EXHAUST
 VENTILATION SYSTEMS SIZED AT A RATE OF 0.75 CFMS PER
 SF. WILL BE REQUIRED- TABLE 403.3.1.1 FBC M.
  
 D) PROVIDE A DUCT LAYOUT PLAN SHOWING THE REQUIRED
 ALTERATIONS TO THE EXISTING SYSTEMS TO ACCOMODATE THE
 NEW ROOMS AND SPACES WITH BALANCED AIR CONDITIONING-
 SECTION 603.1 FBC M.
  
 E) PROVIDE AN AIR DEVICE SCHEDULE.
  
 F) SHOW HOW THE WAREHOUSE IS BEING VENTILATED AND WHAT
 MATERIALS ARE BEING STORED THERE- SEE SECTIONS 401.2,
 402.1 AND TABLE 403.3.1.1.
  
 G) CLARIFY THE USE OF THE CHARGING STATION SHOWN IN THE
 WAREHOUSE OF SHEET EP-1. PLEASE NOTE THAT AN EXHAUST
 VENTILATION SYSTEM IS REQUIRED FOR BATTERY CHARGING
 AREAS PER SECTIONS 502.3- 502.5.3 FBC M.
  
  
 PLEASE NOTE THAT DUE TO THE LACK OF MECHANICAL PLANS
 THERE MAY BE ADDITIONAL COMMENTS WHEN COMPLETE PLANS
 AND CALCULATIONS ARE SUBMITTED.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  