| Date |
Text |
| 2018-10-24 15:55:06 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18081507 |
| | REVIEWED: OCTOBER 24, 2018 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER I |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC ENERGY = FBC ENERGY CONSERVATION |
| | |
| | 1. [FBC AMENDED 109]VALUE OF PROJECT SEEMS LOW AT |
| | $22,500.00. PLEASE INCLUDE VALUE FOR ALL WORK BEING |
| | PERFOMED. |
| | |
| | 2. [FBC EB301.1]WHICH METHOD IS BEING USED FOR |
| | COMPLIANCE? (PRESCRIPTIVE,WORK AREA OR PERFORMANCE) |
| | |
| | 3. [FBC EB501]WHAT IS THE CLASSIFICATION OF NEW WORK? |
| | WHAT WAS THE OCCUPANCY OF THIS SPACE? |
| | WHAT ARE OCCUPANCIES OF ADJACENT SPACES? |
| | |
| | 4. [FBC C503.2]CHANGE IN SPACE CONDITIONING |
| | HOW IS THERMAL ENVELOPE MAINTAINED IN BUSINESS AREA? IS |
| | THE DISPATCH AREA AND STORAGE AREA BEING COOLED? |
| | |
| | 5. [FBC 1013.1 ]WHERE REQUIRED. |
| | EXITS AND EXIT ACCESS DOORS SHALL BE MARKED BY AN |
| | APPROVED EXIT SIGN READILY VISIBLE FROM ANY DIRECTION |
| | OF EGRESS TRAVEL. THE PATH OF EGRESS TRAVEL TO EXITS |
| | AND WITHIN EXITS SHALL BE MARKED BY READILY VISIBLE |
| | EXIT SIGNS TO CLEARLY INDICATE THE DIRECTION OF EGRESS |
| | TRAVEL IN CASES WHERE THE EXIT OR THE PATH OF EGRESS |
| | TRAVEL IS NOT IMMEDIATELY VISIBLE TO THE OCCUPANTS. |
| | INTERVENING MEANS OF EGRESS DOORS WITHIN EXITS SHALL BE |
| | MARKED BY EXIT SIGNS. EXIT SIGN PLACEMENT SHALL BE SUCH |
| | THAT NO POINT IN AN EXIT ACCESS CORRIDOR OR EXIT |
| | PASSAGEWAY IS MORE THAN 100 FEET (30 480 MM) OR THE |
| | LISTED VIEWING DISTANCE FOR THE SIGN, WHICHEVER IS |
| | LESS, FROM THE NEAREST VISIBLE EXIT SIGN. |
| | THE EXIT SIGN AT S.W. LOADING DOCK WOULD NOT BE VISIBLE |
| | WITH STORAGE CRATES. PROVIDE INTERMEDIATE SIGN VISABLE |
| | FROM AISLEWAY. |
| | ALSO, THE EXIT SIGN IN STORAGE THAT LEADS INTO |
| | ACCOUNTS, BUT THEN THERE IS NO EXIT SIGN IN ACCOUNTS. |
| | |
| | 6. [FBC A403.2]SEPARATE FACILITIES |
| | LABEL THE EXISTING BATHROOMS FOR MEN AND WOMEN. |
| | |
| | 7. [FBC A604.3]CLEARANCE |
| | SHOW ADA CLEARANCES AT BATHROOM FIXTURES. |
| | |
| | 8. [FBC A206.1]GENERAL. |
| | ACCESSIBLE ROUTES SHALL BE PROVIDED IN ACCORDANCE WITH |
| | 206 AND SHALL COMPLY WITH CHAPTER 4. |
| | SHOW ACCESSIBLE PATH FROM PARKING TO ACCESSIBLE ENTRY. |
| | |
| | 9.[FBC 1604.1] PROVIDE DETAIL OF NEW 3 HR ROLL UP DOORS |
| | COLUMS TO PICK UP LOAD FROM STEEL ANGLES. |
| | PROVIDE DETAIL OF FOOTING SUPPORT OF NEW 4X4 STEEL |
| | POSTS AT DISPATCH AREA. |
| | |
| | NOTE: |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |