| Plan Review Notes For Permit 18081500 |
| Permit Number |
18081500 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-10-24 12:15:31 | THE FOLLOWING COMMENTS FROM THE FIRST PLUMBING REVIEW | | | HAVE NOT BEEN ADDRESSED. | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FHA = FAIR HOUSING ACT | | | | | | | | | 1. THIS BUILDING WAS CONSTRUCTED UNDER THE REQUIREMENTS | | | OF THE FAIR HOUSING ACT. INDICATE ON THE PLANS WHICH | | | DESIGN SPECIFICATION ( "A" OR 'B" OF THE ACT) WAS USED | | | IN THE ORIGINAL DESIGN OF THIS UNIT. | | | | | | 2. SHOW THE DEPTH OF THE NEW VANITY. THE VANITY SHALL | | | BE A MAXIMUM OF 24 INCHES DEEP PER THE FAIR HOUSING | | | ACT. | | | | | | 3. ADDITIONAL REINFORCEMENT MAY BE REQUIRED IN THE | | | WALLS AROUND THE TUB TO ALLOW FOR THE FUTURE | | | INSTALLATION OF GRAB BARS PER THE FAIR HOUSING ACT. | | | SHOW THE LOCATION OF THE REQUIRED REINFORCEMENTS AND | | | THE MINIMUM WIDTH OF THE REINFORCEMENT AND THE MINIMUM | | | AND MAXIMUM DISTANCES FROM THE FINISH FLOOR. | | | | | | 4) SHOW THE REQUIRED CLEAR FLOOR SPACE FOR THE NEW TUB | | | IN ACCORDANCE WITH THE FAIR HOUSING ACT. | | | | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|