| 2018-09-27 12:58:33 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 1ST REVIEW: |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. IS UNIT ON AN ELEVATED FLOOR? PLEASE CLARIFY. WPB |
| | FPC 107.2.1 |
| | 2. CLOTHES WASHER IS RELOCATED TO ANOTHER WALL. PROVIDE |
| | SANITARY RISER SHOWING HOW THE UNIT DRAINAGE AND |
| | VENTING NOTING POINTS OF CONNECTION TO EXISTING |
| | SYSTEMS; CLOUD NEW WORK. PROVIDE SIZE OF NEW AND |
| | EXISTING PIPING. IF CONNECTING TO ANY EXISTING DRAIN |
| | OTHER THAN THE ORIGINAL, PROVIDE LOAD CALCULATIONS OF |
| | EXISTING SYSTEM, NOTING TYPE (I.E. SOIL STACK, WASTE |
| | STACK VENT) TO CONFIRM THAT EXISTING WILL NOT BE |
| | OVERLOADED. WPB FPC 107.2.1 |
| | 3. IF ON ELEVATED FLOOR THEN PROVIDE PIPING MATERIALS |
| | TYPE & FIRE RATED ASSEMBLIES FOR NEW OR RELOCATED |
| | PIPING FLOOR PENETRATIONS PER WPB FBC 107.2.1 |
| | 4. PROVIDE NOTE STATING "THE VALVES FOR THE STACKABLE |
| | WASHING MACHINE(S) SHALL BE ACCESSIBLE." WPB FPC |
| | 107.2.1 FBC PL 606.3 |
| | 6. PROVIDE WATER HAMMER ARRESTORS AT WATER SUPPLIES TO |
| | ICE LINE, DISHWASHER AND CLOTHES WASHER PER FPC PL |
| | 604.9; INDICATE SAME ON THE PLANS PER WPB FPC 107.2.1 |
| | |
| | |
| | |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID". |
| | |
| | |