| Date |
Text |
| 2018-09-27 10:41:42 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 1ST REVIEW: |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. PROVIDE NOTE STATING "WATER HAMMER ARRESTOR TO BE |
| | INSTALLED IN ACCORDANCE WITH FBC RES P2903.5" |
| | 2. PROVIDE NOTE AT SHOWER STATING "SHOWER CONTROL |
| | VALVE(S) SHALL BE PRESSURE BALANCED PB,THERMOSTATIC |
| | MIXING (TM) OR COMBINATION PB/TM VALVE TYPES WITH HIGH |
| | TEMPERATURE LIMITING STOP." FBC RES P2708.4 |
| | 3. THERMAL EXPANSION DEVICE REQUIRED ON COLD WATER |
| | SUPPLY TO WATER HEATER. A MEANS FOR CONTROLLING |
| | INCREASED PRESSURE CAUSED BY THERMAL EXPANSION SHALL BE |
| | INSTALLED WHERE REQUIRED IN ACCORDANCE WITH SECTIONS |
| | FBC RES P2903.4.2. |
| | 4. PROVIDE NOTE STATING "A WATER HEATER PAN AND DRAIN |
| | IS TO BE INSTALLED IN ACCORDANCE WITH FBC RES P2608.6, |
| | P2801.6.1 & P2801.6.2" |
| | 5. PER P3108.1, THE CLOTHES WASHER DRAIN MAY NOT |
| | DISCHARGE THROUGH THE BATH 2 BATHROOM GROUP. CONNECT |
| | WASHER DRAIN DOWNSTREAM OF GROUP; TUB DRAIN TO CONNECT |
| | WET VENT OR IT IS TO BE REVENTED. |
| | 6. PER P3108.1, THE KITCHEN SINK DRAIN MAY NOT |
| | DISCHARGE THROUGH THE MASTER BATH BATHROOM GROUP. |
| | CONNECT SINK DRAIN DOWNSTREAM OF GROUP; CONNECT |
| | LAVATORY DRAIN TO TUB DRAIN TO COMPLETE WET VENTED |
| | GROUP. ELIMINATE 2" VENT UPSTEAM OF WATER CLOSET. |
| | |
| | |
| | |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID". |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |