| 2018-10-01 17:27:23 | NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW |
| | COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | 1- REVISE THE BALANCED RETURN AIR TRANSFER DUCT SIZE |
| | SPECIFIED FOR SECONDARY BEDROOMS 2 AND 3. NEED AT LEAST |
| | 9" DUCT FOR BEDROOM WITH 7" SUPPLY DUCT AND AT LEAST |
| | 10" DUCT FOR BEDROOM WITH 8" SUPPLY DUCT AS REQUIRED BY |
| | SEC. M1602.3 FBC-RESIDENTIAL. |
| | |
| | 2- PROVIDE THE NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE A/C DESIGN AS REQUIRED BY SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |
| | 3- REVISE THE HVAC LOAD CALCULATIONS: |
| | A) THE FRONT DOOR OF THIS HOUSE DOESN'T FACE SOUTHEAST. |
| | ACCORDING TO SEC. R403.7.1 FBC-ENERGY CONSERVATION |
| | CALCULATIONS NEED TO BE DONE BASED ON THE ACTUAL |
| | ORIENTATION OF THE BUILDING. |
| | |
| | B) CALCULATIONS ARE PREPARED BY GOARCH ENGINEERING, |
| | INC. THE ENGINEER NEEDS TO SIGN AND SEAL CALCULATIONS |
| | AS REQUIRED BY SEC. 61G15-23.001 FAC AND CHAPTER 471 |
| | F.S. WHEN SUBMITTING DOCUMENTS FOR PUBLIC RECORDS. |
| | |
| | |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. |
| | |
| | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY |
| | REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS. |
| | |