2018-09-05 11:03:45PERMIT #18081451
 FIRE REVIEW COMMENTS
  
 FAILED COMMENTS:
  
 1) CLARIFICATION NEEDED ON WHAT IS TO BE ANTICIPATED AS
 PART OF THE PHASING PLANS. PLEASE PROVIDE A NARRATIVE
 EXPLANATION OF PHASING PLAN. PLEASE INCLUDE, AT A
 MINIMUM:
 A) WHAT, IF ANY, PART OF THE STORE WILL BE OPEN TO THE
 PUBLIC AND/OR STORE EMPLOYEES DURING EACH PHASE.
 B) HOW WILL CUSTOMERS AND STORE EMPLOYEES BE KEPT OUT
 OF CONSTRUCTION AREAS DURING PHASING WORK.
 C) ALL REQUIRED FIRE AND LIFE SAFETY SYSTEMS SHALL BE
 FULLY OPERATIONAL PRIOR TO OCCUPANCY.
 D) WHAT ARE THE ANTICIPATED PHASING DATES/ TIME FRAMES?
 E) PHASE 4 APPEARS TO APPLY TO THE MAIN POINT OF ENTRY
 AND EGRESS, WILL THIS ACCESS POINT BE OPEN TO THE
 PUBLIC DURING CONSTRUCTION OF PHASE 4? IF SO, HOW WILL
 CUSTOMERS BE PROTECTED FROM CONSTRUCTION WORK?
 F) THE RESTROOMS ARE LOCATED IN PHASE 3, WILL THEY BE
 ACCESSIBLE DURING CONSTRUCTION OF THIS PHASE? IF SO,
 WHAT KEEPS PATRONS/EMPLOYEES FROM ACCESSING THE
 CONSTRUCTION AREA?
  
 2) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved