| Plan Review Notes For Permit 18081451 |
| Permit Number |
18081451 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-09-07 08:01:51 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. THE PHASING PLAN IS NOT CLEAR. FBC B 3302.1, WILL | | | PHASE 01 BE OPEN DURING PHASE 02 CONSTRUCTION? IF YES, | | | HOW WILL EXIT LIGHTING BE AFFECTED? PROVIDE A NARRATIVE | | | WHICH EXPLAINS THE PHASING. | | | | | | | | | | | | |
|