| 2018-10-05 13:32:09 | ORIGINAL COMMENTS WERE NOT ADDRESSED: | | | | | | INSUFFICIENT INFORMATION - PLEASE PROVIDE | | | "MANUFACTURER'S SPECIFICATION SHEETS" FOR THE NOZZLES | | | AND FUSIBLE LINKS. | | | RE-EVALUATE NUMBER OF FLOWS USED. | | | PROVIDE AN IN DEPTH LAYOUT OF MACHINERY AND DEVICE | | | PLACEMENT, AS IT APPEARS THAT THERE ARE NOZZLES ABOVE | | | THE PLENUM. | | | | | | S. THOMAS | | | 561-804-4728 |
|