Plan Review Notes
Plan Review Notes For Permit 18081417
Permit Number 18081417
Review Stop P
Sequence Number 2
Notes
Date Text
2018-11-01 11:06:041) THERE ARE TWO DIFFERENT SIGNED AND SEALED POOL
 DRAWINGS IN THE SUBMITTAL PACKAGE. ONE IS BY CHARLES
 R.ADAMS AND ONE IS BY G.B. COLLINS ENGINEERING. REMOVE
 THE DRAWING THAT IS NOT APPLICABLE FROM THIS PACKAGE
 AND SUBMIT TWO COMPLETE SETS OF PLANS FOR SUBMITTAL.
 FBC SEC. 107.1.
 2) SPECIFICATIONS HAVE BEEN SUBMITTED FOR TWO DIFFERENT
 PUMPS AND FILTERS. REMOVE ALL OLD DOCUMENTS FROM THE
 SUBMITTAL PACKAGE AND SUBMIT TWO COMPLETE SETS OF
 DOCUMENTS FOR REVIEW. FBC SEC. 107.1.
 3) A SIMPLIFIED TOTAL DYNAMIC HEAD WORKSHEET SIGNED AND
 SEALED BY RICHARD TOMMELL HAS BEEN SUBMITTED. THE 2013
 EDITION OF ANSI/APSP/ICC-7 2013 DOES NOT ALLOW THIS
 METHOD TO BE USED FOR CALCULATION OF MAXIMUM SYSTEM
 FLOW RATE. REFER TO THE OPTIONS IN SEC. 4.4.9.1 OF THE
 AFOREMENTIONED CODE. THE RESPONSE LETTER FROM G.B.
 COLLINS ENGINEERING STATES THAT THE REASON FOR NOT
 ALLOWING THE SIMPLIFIED TDH METHOD IS UNCLEAR. PLEASE
 REFER TO THE AFOREMENTIONED STANDARD AND CODE SECTION.
 THE SIMPLIFIED TDH METHOD DEFINITION IS NO LONGER IN
 APSP-7 2013. SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS IN
 ACCORDANCE WITH APSP-7 2013. 2ND REQUEST.
 4) PLAN BY G.B. COLLINS - UNDER "GENERAL DESIGN
 REQUIREMENTS" NOTES REFERS TO ONE RETURN INLET PER 600
 SQ. FT. 2017 FBC-RES. SEC. R4501.21.5 REQUIRES ONE
 RETURN EVERY 300 SQ. FT. REVISE THE NOTE.
 5) SHOW THE COMPLETE SPA PIPING LAYOUT ON THE PLAN FROM
 G.B.COLLINS IF THAT IS THE PLAN TO BE SUBMITTED FOR
 PERMIT.FBC 107.2.1.
 6) SIZE ALL SECTIONS OF THE POOL AND SPA PIPING ON THE
 PLAN FROM G.B. COLLINS IF THAT IS THE PLAN TO BE
 SUBMITTED FOR PERMIT.FBC 107.2.1. FBC 107.2.1.
 7) SHOW ON THE PLAN FROM G.B. COLLINS IF THERE ARE ANY
 MAIN DRAINS ON THE POOL IF THAT IS THE PLAN TO BE
 SUBMITTED FOR PERMIT.FBC 107.2.1. FBC 107.2.1.
 8) THE POOL PLAN FROM G.B. COLLINS REFERS TO FLORIDA
 BUILDING CODE SEC.R4101. THIS SECTION IS FOR ELECTRICAL
 APPLIANCE INSTALLATION AND HAS NOTHING TO DO WITH THE
 POOL CODE. REVISE THE NOTE TO READ THE CORRECT SECTION
 OF THE FBC. FBC 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  