| 2018-11-01 11:06:04 | 1) THERE ARE TWO DIFFERENT SIGNED AND SEALED POOL |
| | DRAWINGS IN THE SUBMITTAL PACKAGE. ONE IS BY CHARLES |
| | R.ADAMS AND ONE IS BY G.B. COLLINS ENGINEERING. REMOVE |
| | THE DRAWING THAT IS NOT APPLICABLE FROM THIS PACKAGE |
| | AND SUBMIT TWO COMPLETE SETS OF PLANS FOR SUBMITTAL. |
| | FBC SEC. 107.1. |
| | 2) SPECIFICATIONS HAVE BEEN SUBMITTED FOR TWO DIFFERENT |
| | PUMPS AND FILTERS. REMOVE ALL OLD DOCUMENTS FROM THE |
| | SUBMITTAL PACKAGE AND SUBMIT TWO COMPLETE SETS OF |
| | DOCUMENTS FOR REVIEW. FBC SEC. 107.1. |
| | 3) A SIMPLIFIED TOTAL DYNAMIC HEAD WORKSHEET SIGNED AND |
| | SEALED BY RICHARD TOMMELL HAS BEEN SUBMITTED. THE 2013 |
| | EDITION OF ANSI/APSP/ICC-7 2013 DOES NOT ALLOW THIS |
| | METHOD TO BE USED FOR CALCULATION OF MAXIMUM SYSTEM |
| | FLOW RATE. REFER TO THE OPTIONS IN SEC. 4.4.9.1 OF THE |
| | AFOREMENTIONED CODE. THE RESPONSE LETTER FROM G.B. |
| | COLLINS ENGINEERING STATES THAT THE REASON FOR NOT |
| | ALLOWING THE SIMPLIFIED TDH METHOD IS UNCLEAR. PLEASE |
| | REFER TO THE AFOREMENTIONED STANDARD AND CODE SECTION. |
| | THE SIMPLIFIED TDH METHOD DEFINITION IS NO LONGER IN |
| | APSP-7 2013. SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS IN |
| | ACCORDANCE WITH APSP-7 2013. 2ND REQUEST. |
| | 4) PLAN BY G.B. COLLINS - UNDER "GENERAL DESIGN |
| | REQUIREMENTS" NOTES REFERS TO ONE RETURN INLET PER 600 |
| | SQ. FT. 2017 FBC-RES. SEC. R4501.21.5 REQUIRES ONE |
| | RETURN EVERY 300 SQ. FT. REVISE THE NOTE. |
| | 5) SHOW THE COMPLETE SPA PIPING LAYOUT ON THE PLAN FROM |
| | G.B.COLLINS IF THAT IS THE PLAN TO BE SUBMITTED FOR |
| | PERMIT.FBC 107.2.1. |
| | 6) SIZE ALL SECTIONS OF THE POOL AND SPA PIPING ON THE |
| | PLAN FROM G.B. COLLINS IF THAT IS THE PLAN TO BE |
| | SUBMITTED FOR PERMIT.FBC 107.2.1. FBC 107.2.1. |
| | 7) SHOW ON THE PLAN FROM G.B. COLLINS IF THERE ARE ANY |
| | MAIN DRAINS ON THE POOL IF THAT IS THE PLAN TO BE |
| | SUBMITTED FOR PERMIT.FBC 107.2.1. FBC 107.2.1. |
| | 8) THE POOL PLAN FROM G.B. COLLINS REFERS TO FLORIDA |
| | BUILDING CODE SEC.R4101. THIS SECTION IS FOR ELECTRICAL |
| | APPLIANCE INSTALLATION AND HAS NOTHING TO DO WITH THE |
| | POOL CODE. REVISE THE NOTE TO READ THE CORRECT SECTION |
| | OF THE FBC. FBC 107.2.1. |
| | |