| 2018-09-17 11:06:56 | 1) THE SIMPLIFIED TOTAL DYNAMIC HEAD CALCULATION METHOD |
| | IS NO LONGER PERMITTED BY APSP 7- 2013. THEREFORE, THE |
| | SUBMITTTED TOTAL DYNAMIC HEAD CALCULATION SHEET IS |
| | UNACCEPTABLE. SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS |
| | FOR THE MAXIMUM SYSTEM FLOW. THE MAXIMUM FLOW OF THE |
| | PUMP FROM ITS PUMP CURVE IS NO LONGER ALLOWED TO BE |
| | USED IN DETERMINING MAXIMUM SYSTEM FLOW RATE PER |
| | ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE 2013 |
| | EDITION ADDRESSES FLOW RATE IN GALLONS PER MINUTE |
| | (GPM). IT REQUIRES THAT MAXIMUM SYSTEM FLOW RATE DOES |
| | NOT EXCEED THE LISTED MAXIMUM FLOW RATE OF THE SUCTION |
| | OUTLET FITTING ASSEMBLY (DRAIN COVER).THE TDH |
| | CALCULATIONS MUST INCLUDE ALL OF THE SYSTEM COMPONENTS |
| | INCLUDING SUCTION AND RETURN PIPING, FITTINGS, VALVES, |
| | HEATER, FILTER, AND CHLORINATOR. ALL SYSTEM COMPONENTS |
| | EXCEPT THE PUMP. |
| | 2) SUBMIT TWO LEGIBLE COPIES OF THE POOL PUMP CURVE. |
| | IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS SPECIFIC |
| | TO THE PUMP BEING INSTALLED ON THIS POOL. THIS IS |
| | NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE TDH |
| | CALCULATIONS |
| | 3) INDICATE ON THE PUMP CURVE WHICH CURVE KEY IS FOR |
| | THE PUMP BEING INSTALLED ON THIS SYSTEM. WPB AMEND. TO |
| | FBC SEC. 107.2.1. |
| | 4) INDICATE ON THE POOL EQUIPMENT DOCUMENTS WHICH MODEL |
| | FILTER IS BEING INSTALLED. 2017 FBC SEC. 107.2.1. |
| | 5) INDICATE ON THE POOL EQUIPMENT DOCUMENTS WHICH MODEL |
| | PUMP IS BEING INSTALLED. 2017 FBC SEC. 107.2.1. |
| | 6) SUBMIT TWO COPIES OF THE MANUFACTURER'S |
| | SPECIFICATIONS FOR THE POOL MAIN DRAINS. 2017 FBC SEC. |
| | 107.2.1. |
| | 7) THE PRINTING ON THE SUBMITTTED SIGNED AND SEALED |
| | PLANS BY CHARLES ADAMS IS BARELY LEGIBLE. SUBMIT TWO |
| | LEGIBLE COPIES OF THE DOCUMENTS SIGNED AND SEALED BY |
| | CHARLES ADAMS FOR REVIEW. 2017 FBC SEC. 107.2.1, FL. |
| | ADMIN. CODE RULE 61G15-23.001. |
| | 8) THE PIPE SIZES ARE MISSING FROM THE PIPING SCHEMATIC |
| | ON THE DDRAWINGS FROM MR. ADAMS, ENGINEER. 2017 FBC |
| | SEC. 107.2.1. |
| | 9) SHT. 2 - NOTES - THE STANDARDS LISTED IN NOTE 13 OF |
| | PLANS FROM CHARLES ADAMS ARE OUTDATED. REVISE THE NOTE. |
| | THE FOLLOWING STANDARDS ARE IN EFFECT: |
| | ANSI/NSPI 3 - 2015 |
| | ANSI/NSPI 5 - 2011 |
| | ANSI/NSPI 7 - 2013 |
| | 10) INDICATE ON SHT. 2 OF THE PLANS FROM CHARLES |
| | EDWARDS WHICH MODEL OF THE POOL IS BEING INSTALLED. |
| | 2017 FBC SEC. 107.2.1. |
| | 11) SHT. 2, NOTE #19 OF PLANS BY CHARLES ADAMS STATES |
| | THAT THE PIPE SIZING AND HYDRAULIC VELOCITY WERE DONE |
| | BY THE CONTRACTOR. CLARIFY. THE ENGINEER OF RECORD IS |
| | RESPONSIBLE FOR THE DESIGN OF THE POOL. FL. ADMIN. CODE |
| | RULE 61G15-30.003. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |