2018-09-26 07:37:33PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PROVIDE SIGNED AND SEALED ENGINEERING TO SPECIFY THE
 REQUIRED LOCATIONS OF THE 30" X 30" CONCRETE DEADMAN
 ANCHORS. 107.2.1.2
  
 2) THERE IS A DIFFERENCE BETWEEN THE SIGNED AND SEALED
 ENGINEERING AND THE OTHER DRAWINGS. THE POOL SHAPE AND
 CROSS SECTIONS OF THE POOLS DO NOT MATCH. FBC107.2.1
  
 3) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 4) THE ADDRESS OF THE PROJECT IS REQUIRED ON THE
 DRAWINGS. FBC 107.2.1
  
 5) THE BLOCK DECO WALL DRAWINGS ARE MISSING
 INFORMATION. PROVIDE AN ELEVATION DRAWING OF THE WALL.
 SPECIFY THE SPACING OF THE VERTICAL REBAR AND THE
 SPACING OF THE CROSS BARS IN THE FOOTING. VERTICAL
 REINFORCING IS REQUIRED AT EACH END OF THE WALL. A BOND
 BEAM WITH HORIZONTAL REINFORCING IS REQUIRED AT THE TOP
 OF THE WALL. CLARIFY THE WIDTH AND THICKNESS OF THE
 FOOTER. A 12" WIDE FOOTER IS NOT ADEQUATE FOR THE 8"
 CONCRETE BLOCK WALL WITHOUT ENGINEERING. THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN IS
 REQUIRED ON ALL DRAWINGS. FBC 107.2.1
  
  