Plan Review Notes For Permit 18081402
Permit Number 18081402
Review Stop M
Sequence Number 2
Notes
Date Text
2019-01-03 10:18:36PASS PROVISO
 1) PROVIDE RETURN AIR IN STAFF ROOM # 7
 PER SECTION 601.6 BALANCED RETURN AIR.
 2017 FBC (M)
 2) REFER TO SECTION 601.6 BALANCED RETURN AIR
 IN RECEPTION ROOM. 2017 FBC (M)
 3) REFER TO SECTION 606.2 WHERE REQUIRED
 PROVIDE LITERATURE ON AIR HANDLER # 1 SHOWING
 FAN SPEEDS.
 HAVE INFORMATION ON SITE AT 1ST INSPECTION.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676