| 2018-11-13 09:51:41 | 1ST REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. THE SINGLE OCCUPANT BATHROOM IN THE PRIVATE OFFICE |
| | #2 IS REQUIRED TO COMPLY WITH SOME ACCESSIBILITY. |
| | A) THE DOOR SHALL COMPLY WITH FBC ACC 603.2.3 EXCEPTION |
| | #1. |
| | B) THE EXCEPTIONS FOR THE SINGLE OCCUPANT BATHROOM ARE |
| | THE FOLLOWING. |
| | 1) THE HEIGHT OF THE TOILET FBC ACC 604.4 EXCEPTION #1 |
| | 2) THE GRAB BAR DO NOT NEED TO BE INSTALLED BUT THE |
| | REINFORCEMENT BACKING SHALL BE INSTALLED IN THE WALLS. |
| | FBC ACC 604.5 EXCEPTION #1 |
| | 3) THE LAVATORY FBC ACC 606.2 EXCEPTION #2 606.3 |
| | EXCEPTION #1 |
| | C) !!!!THESE ARE REQUIRED SHOW COMPLIANCE WITH THE |
| | FOLLOWING!!!! |
| | 1) THE TOILET SHALL COMPLY WITH FBC ACC 604.2 |
| | LOCATION.THE WATER CLOSET SHALL BE POSITIONED WITH A |
| | WALL OR PARTITION TO THE REAR AND TO ONE SIDE. THE |
| | CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES (405 |
| | MM) MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL OR |
| | PARTITION, |
| | 2) THE TOILET SHALL COMPLY WITH FBC ACC 604.3.1 SIZE. |
| | CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES |
| | MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND |
| | 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR |
| | WALL. |
| | AND FBC ACC 604.3.2 OVERLAP. THE REQUIRED CLEARANCE |
| | AROUND THE WATER CLOSET SHALL BE PERMITTED TO OVERLAP |
| | THE WATER CLOSET, ASSOCIATED GRAB BARS, DISPENSERS, |
| | SANITARY NAPKIN DISPOSAL UNITS, COAT HOOKS, SHELVES, |
| | ACCESSIBLE ROUTES, CLEAR FLOOR SPACE AND CLEARANCES |
| | REQUIRED AT OTHER FIXTURES, AND THE TURNING SPACE. NO |
| | OTHER FIXTURES OR OBSTRUCTIONS SHALL BE LOCATED WITHIN |
| | THE REQUIRED WATER CLOSET CLEARANCE. |
| | |
| | 2. ALL BATHROOMS SHALL COMPLY WITH FBC ACC 604.7 |
| | DISPENSERS. TOILET PAPER DISPENSERS SHALL COMPLY WITH |
| | 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9 INCHES |
| | MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO THE |
| | CENTERLINE OF THE DISPENSER. |
| | |
| | 3. THE GRAB BARS IN THE COMMON BATHROOMS SHALL COMPLY |
| | WITH FBC ACC 604.5.1 SIDE WALL. THE SIDE WALL GRAB BAR |
| | SHALL BE 42 INCHES LONG MINIMUM, LOCATED 12 INCHES |
| | MAXIMUM FROM THE REAR WALL AND EXTENDING 54 INCHES |
| | MINIMUM FROM THE REAR WALL. |
| | 604.5.2 REAR WALL. THE REAR WALL GRAB BAR SHALL BE 36 |
| | INCHES LONG MINIMUM AND EXTEND FROM THE CENTERLINE OF |
| | THE WATER CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 |
| | INCHES MINIMUM ON THE OTHER SIDE. |
| | |
| | 4. THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE |
| | GRIPPING SURFACE. PER FBC ACC 609.4 |
| | |
| | 5. THE BREAK ROOM SINK SHALL COMPLY WITH FBC ACC 606.2 |
| | CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE COMPLYING WITH, |
| | POSITIONED FOR A FORWARD APPROACH, AND KNEE AND TOE |
| | CLEARANCE COMPLYING WITH SHALL BE PROVIDED. |
| | 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE INSTALLED |
| | WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER |
| | SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR |
| | GROUND |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |