Plan Review Notes
Plan Review Notes For Permit 18081402
Permit Number 18081402
Review Stop B
Sequence Number 1
Notes
Date Text
2018-11-16 13:16:17NEW BUILDING (GROUP B) BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1-ART IN PUBLIC SPACES.
 PLEASE REVIEW ART IN PUBLIC PLACES. THE CITY OF WEST
 PALM BEACH ART IN PUBLIC PLACES ORDINANCE REQUIREMENT
 THAT APPLIES TO ANY REMODEL OR NEW CONSTRUCTION PROJECT
 FOR WHICH THE PERMIT APPLICATION WAS SUBMITTED AFTER
 6/29/14, AND THE TOTAL PROJECT CONSTRUCTION COSTS ARE
 EQUAL TO OR GREATER THAN $750,000 WILL NEED TO COMPLY
 WITH THIS ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR
 822-1515 E-MAIL: [email protected]
  
 2- IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 3- PROVIDE COPY OF SOIL TEST REPORT SPECIFIED ON
 FOUNDATION NOTES ON SHEET S.03.
 SEC. 1803.1 FBC.
  
 4- SITE PLAN ON SHEET A.02 SHOWS 10'X20' LOADING ZONE
 IN THE MIDDLE OF THE PARKING LOT. THIS LOADING AREA IS
 BLOCKING THE ACCESSIBLE PARKING SPACE. REVISE AS
 REQUIRED. SEC. 206.1 FBC-ACCESSIBILITY.
  
 5- ENERGY CALCULATIONS:
 A) PLANS NEED TO SPECIFY THE INSULATION R VALUE OF
 EXTERIOR WALLS. NOTE: ARCHITECT AND ENGINEER PREPARING
 THE ENERGY CALCULATIONS TO COORDINATE INFORMATION TO
 AVOID CONFLICTS/DELAYS. THIS APPLIES TO CEILING
 INSULATION ALSO. SEC. C103.2 FBC-ENERGY CONSERVATION.
  
 B)ARCHITECT OF RECORD TO CERTIFY (SIGNATURE AND LICENSE
 NUMBER) ON ENERGY FORM AS REQUIRED BY SEC. C103.1.1.1.2
 FBC-ENERGY CONSERVATION.
  
 C) THE BUILDING OWNER OR LEGALLY AUTHORIZED AGENT NEEDS
 TO CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE
 ENERGY CODE AS REQUIRED BY SEC. C103.1.1.2 FBC-ENERGY
 CONSERVATION PRIOR TO RECEIVING THE PERMIT TO BEGIN
 CONSTRUCTION.
  
 D) ENGINEER OF RECORD PERFORMING THE ENERGY
 CALCULATIONS TO COORDINATE WITH ARCHITECTURAL PLANS TO
 AVOID CONFLICTS/DELAYS. INFORMATION FOR WALLS AND
 CEILING INSULATION R VALUE DOESN'T MATCH. SEC. 107.2.1
 CITY AMENDMENTS. ALSO, CHECK THE PROPER BOXES IN THE
 MANDATORY SECTION.
  
 6- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 INTERIOR WINDOWS SHOWN ON FLOOR PLANS. INCLUDE FRAMING
 DETAILS AND GLAZING SPECIFICATIONS. SEC. 2406 FBC.
  
 7- SHEET A.08: PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR THE FASTENING OF THE METAL PARAPET
 CAP AND (2)2X10P.T. WOOD BLOCKING. SEC. 1609.1 FBC.
  
 8- LADDER TO ACCESS A/C EQUIPMENT ON THE UPPER ROOF
 NEED TO EXTEND NOT LESS THAN 30INCHES. LADDERS NEED TO
 BE CONSTRUCTED AS REQUIRED BY SEC. 306.5
 FBC-MECHANICAL. (SEE SEC. 1011.16 FBC). NOTE:
 COORDINATE WITH MECHANICAL PLANS EXAMINER/INSPECTOR TO
 AVOID CONFLICTS/ DELAYS.
  
 9- CLARIFY IF TENANT SEPARATION WALL BETWEEN
 MISCELLANEOUS SPACE 1 AND MISCELLANEOUS SPACE 2 IS
 GOING TO BE A FIRE RATED WALL OR NOT. WALL TYPE 5 ON
 SHEET A.06 DOESN'T PROVIDE SPECS FOR A FIRE RATED
 ASSEMBLY BUT LIFE SAFETY PLAN ON SHEET A.14 SPECIFIES
 THAT IT IS A FIRE RATED WALL. REVISE/CLARIFY AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 10- DUMPSTER STRUCTURAL PLANS SHOWN ON SHEET A.03 DON'T
 MATCH STRUCTURAL PLANS SHOWN ON SHEET S.01. REVISE AS
 REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 11- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 A) ALL EXTERIOR DOORS AS SHOWN ON PLANS.
  
 B) ALL WINDOWS AS SHOWN ON PLANS.
  
 C)FLAT ROOF FOR METAL DECK AND CONCRETE DECK AS SHOWN
 ON PLANS. . AND, CLEARLY MARK WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. 1609 FBC. NOTE: IF THE
 SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES FOR
 ALL ROOF ZONES, THEN SIGNED AND SEALED RAS 117
 CALCULATIONS ARE REQUIRED.
  
 D) PRECAST LINTELS AS SHOWN ON PLANS.
  
 E) HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
  
 12- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]