| 2018-11-16 13:16:17 | NEW BUILDING (GROUP B) BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | 1-ART IN PUBLIC SPACES. |
| | PLEASE REVIEW ART IN PUBLIC PLACES. THE CITY OF WEST |
| | PALM BEACH ART IN PUBLIC PLACES ORDINANCE REQUIREMENT |
| | THAT APPLIES TO ANY REMODEL OR NEW CONSTRUCTION PROJECT |
| | FOR WHICH THE PERMIT APPLICATION WAS SUBMITTED AFTER |
| | 6/29/14, AND THE TOTAL PROJECT CONSTRUCTION COSTS ARE |
| | EQUAL TO OR GREATER THAN $750,000 WILL NEED TO COMPLY |
| | WITH THIS ORDINANCE. |
| | PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND |
| | CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, |
| | ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION |
| | 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL |
| | PROJECT CONSTRUCTION COST. |
| | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE |
| | V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND |
| | NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO |
| | THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| | PROJECTS. |
| | FOR CONTACT INFORMATION PLEASE CONTACT: |
| | MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR |
| | 822-1515 E-MAIL: [email protected] |
| | |
| | 2- IMPACT FEES - DIGITAL SUBMITTALS |
| | |
| | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE |
| | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS |
| | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST |
| | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE |
| | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL |
| | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME |
| | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM |
| | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS |
| | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF |
| | |
| | 3- PROVIDE COPY OF SOIL TEST REPORT SPECIFIED ON |
| | FOUNDATION NOTES ON SHEET S.03. |
| | SEC. 1803.1 FBC. |
| | |
| | 4- SITE PLAN ON SHEET A.02 SHOWS 10'X20' LOADING ZONE |
| | IN THE MIDDLE OF THE PARKING LOT. THIS LOADING AREA IS |
| | BLOCKING THE ACCESSIBLE PARKING SPACE. REVISE AS |
| | REQUIRED. SEC. 206.1 FBC-ACCESSIBILITY. |
| | |
| | 5- ENERGY CALCULATIONS: |
| | A) PLANS NEED TO SPECIFY THE INSULATION R VALUE OF |
| | EXTERIOR WALLS. NOTE: ARCHITECT AND ENGINEER PREPARING |
| | THE ENERGY CALCULATIONS TO COORDINATE INFORMATION TO |
| | AVOID CONFLICTS/DELAYS. THIS APPLIES TO CEILING |
| | INSULATION ALSO. SEC. C103.2 FBC-ENERGY CONSERVATION. |
| | |
| | B)ARCHITECT OF RECORD TO CERTIFY (SIGNATURE AND LICENSE |
| | NUMBER) ON ENERGY FORM AS REQUIRED BY SEC. C103.1.1.1.2 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | C) THE BUILDING OWNER OR LEGALLY AUTHORIZED AGENT NEEDS |
| | TO CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE |
| | ENERGY CODE AS REQUIRED BY SEC. C103.1.1.2 FBC-ENERGY |
| | CONSERVATION PRIOR TO RECEIVING THE PERMIT TO BEGIN |
| | CONSTRUCTION. |
| | |
| | D) ENGINEER OF RECORD PERFORMING THE ENERGY |
| | CALCULATIONS TO COORDINATE WITH ARCHITECTURAL PLANS TO |
| | AVOID CONFLICTS/DELAYS. INFORMATION FOR WALLS AND |
| | CEILING INSULATION R VALUE DOESN'T MATCH. SEC. 107.2.1 |
| | CITY AMENDMENTS. ALSO, CHECK THE PROPER BOXES IN THE |
| | MANDATORY SECTION. |
| | |
| | 6- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR |
| | INTERIOR WINDOWS SHOWN ON FLOOR PLANS. INCLUDE FRAMING |
| | DETAILS AND GLAZING SPECIFICATIONS. SEC. 2406 FBC. |
| | |
| | 7- SHEET A.08: PROVIDE COMPLETE DETAILS AND |
| | SPECIFICATIONS FOR THE FASTENING OF THE METAL PARAPET |
| | CAP AND (2)2X10P.T. WOOD BLOCKING. SEC. 1609.1 FBC. |
| | |
| | 8- LADDER TO ACCESS A/C EQUIPMENT ON THE UPPER ROOF |
| | NEED TO EXTEND NOT LESS THAN 30INCHES. LADDERS NEED TO |
| | BE CONSTRUCTED AS REQUIRED BY SEC. 306.5 |
| | FBC-MECHANICAL. (SEE SEC. 1011.16 FBC). NOTE: |
| | COORDINATE WITH MECHANICAL PLANS EXAMINER/INSPECTOR TO |
| | AVOID CONFLICTS/ DELAYS. |
| | |
| | 9- CLARIFY IF TENANT SEPARATION WALL BETWEEN |
| | MISCELLANEOUS SPACE 1 AND MISCELLANEOUS SPACE 2 IS |
| | GOING TO BE A FIRE RATED WALL OR NOT. WALL TYPE 5 ON |
| | SHEET A.06 DOESN'T PROVIDE SPECS FOR A FIRE RATED |
| | ASSEMBLY BUT LIFE SAFETY PLAN ON SHEET A.14 SPECIFIES |
| | THAT IT IS A FIRE RATED WALL. REVISE/CLARIFY AS |
| | REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 10- DUMPSTER STRUCTURAL PLANS SHOWN ON SHEET A.03 DON'T |
| | MATCH STRUCTURAL PLANS SHOWN ON SHEET S.01. REVISE AS |
| | REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 11- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| | 61G20-3.001 FOR: |
| | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| | SUBMITTAL) |
| | |
| | A) ALL EXTERIOR DOORS AS SHOWN ON PLANS. |
| | |
| | B) ALL WINDOWS AS SHOWN ON PLANS. |
| | |
| | C)FLAT ROOF FOR METAL DECK AND CONCRETE DECK AS SHOWN |
| | ON PLANS. . AND, CLEARLY MARK WHICH APPROVED ASSEMBLY |
| | IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE |
| | DESIGN PRESSURES OF SEC. 1609 FBC. NOTE: IF THE |
| | SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES FOR |
| | ALL ROOF ZONES, THEN SIGNED AND SEALED RAS 117 |
| | CALCULATIONS ARE REQUIRED. |
| | |
| | D) PRECAST LINTELS AS SHOWN ON PLANS. |
| | |
| | E) HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE |
| | IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION |
| | SCHEDULE. SEE CITY SAMPLE. |
| | |
| | 12- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |