| 2018-10-04 09:45:15 | BUILDING PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER, PX3169 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. LIFE SAFETY PLAN LS-1W SUBMITTED FOR REVIEW DOES NOT |
| | INDICATE LOCATION OF PROPOSED CONNECTION BRIDGE. |
| | 2. PROVIDE FLOOR PLAN WITH ELEVATIONS IDENTIFYING |
| | LOCATION OF PROPOSED CONNECTION BRIDGE. |
| | 3. UPDATED UL ASSEMBLY SPECIFIES FIRE CAULKING BY 3M |
| | COMPANY, TYPES FB 1000 NS, FB 1003 SL, FB 2000 AND FB |
| | 2000 PLUS. ORIGINAL PERMITTED DOCUMENTS SPECIFIES FIRE |
| | CAULKING TO BE ONE SOURCED, SPECIFICALLY HILTI PRODUCTS |
| | FS ONE. PLEASE CLARIFY. |
| | 4. DETAIL FOR CONNECTING BRIDGE SUBMITTED FOR REVIEW |
| | INDICATES BRIDGE WILL BE SITE BUILT. |
| | WELDED OR BOLTED CONNECTIONS |
| | THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE |
| | SPECIFICATIONS & WELDER OPERATOR PERFORMANCE |
| | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| | STANDARDS AT TIME OF INSPECTION. |
| | 2017 FBC-B 2204.1 WELDING |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED AND MARK VOID. |
| | |
| | |