| Date |
Text |
| 2018-09-05 07:16:02 | ****PROVISOS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. SHEET S1, I WAS UNABLE TO LOCATE A SPECIFICATION FOR |
| | F5, EITHER REVISE PLAN TO INCLUDE OR DIRECT AS TO WHERE |
| | THIS CAN BE LOCATED.2 |
| | 6. FBC B 107.2.5, IT APPEARS THAT THIS IS LOCATED IN |
| | SFHA 7' NAVD88. S1 REFERS TO ARCHITECTURAL PAGES FOR |
| | ELEVATION; REVISE A1.1.1 TO INCLUDE (9' NAVD88 MINIMUM |
| | IS REQUIRED). |
| | |
| | 2. FBC B 107.3.5.1.1(1), PROVIDE A "CONSTRUCTION |
| | DOCUMENTS" ELEVATION CERTIFICATE. |
| | |
| | 3. PRIOR TO CONCRETE POUR, A "BUILDING UNDER |
| | CONSTRUCTION" ELEVATION CERTIFICATE WILL BE REQUIRED. |
| | THIS MAY BE SENT VIA EMAIL FOR PRELIMINARY REVIEW. |
| | PRIOR TO FINAL INSPECTION BUT AFTER ALL MECHANICAL |
| | EQUIPMENT HAS BEEN INSTALLED AND FINAL GRADES |
| | COMPLETED, A "FINISHED CONSTRUCTION" ELEVATION |
| | CERTIFICATE WILL BE REQUIRED. THIS MAY BE SENT VIA |
| | EMAIL FOR PRELIMINARY REVIEW. |
| | |
| | 4. THIS PERMIT IS ISSUED AT APPLICANT'S RISK PER FBC |
| | 105.13: |
| | |
| | PHASED PERMIT APPROVAL. AFTER SUBMITTAL OF THE |
| | APPROPRIATE CONSTRUCTION DOCUMENTS, THE BUILDING |
| | OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT FOR THE |
| | CONSTRUCT ION OF FOUNDATIONS OR ANY OTHER PART OF A |
| | BUILDING OR STRUCTURE BEFORE THE CONSTRUCTION DOCUMENTS |
| | FOR THE WHOLE BUILDING OR STRUCTURE HAVE BEEN |
| | SUBMITTED. THE HOLDER OF SUCH PERMIT FOR THE FOUNDATION |
| | OR OTHER PARTS OF A BUILDING OR STRUCTURE SHALL PROCEED |
| | AT THE HOLDER'S OWN RISK WITH THE BUILDING OPERATION |
| | AND WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE |
| | STRUCTURE WILL BE GRANTED. CORRECTIONS MAY BE REQUIRED |
| | TO MEET THE REQUIREMENTS OF THE TECHNICAL CODES. THIS |
| | PROVISION IS ONLY FOR THE FLORIDA BUILDING CODE. ALL |
| | OTHER AGENCY APPROVALS NECESSARY FOR CONSTRUCTION MUST |
| | BE SECURED PRIOR TO THIS PROVISION BEING APPLIED. |
| | |
| | 5. SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE |
| | REQUIRED FOR THE FOLLOWING ITEMS AS APPLICABLE: |
| | LIGHT POLES/SITE LIGHTING |
| | FIRE ALARM |
| | FIRE SPRINKLER |
| | LOW VOLTAGE |
| | ACCESS |
| | LANDSCAPING |
| | IRRIGATION |
| | ALL OTHER ITEMS OTHER THAN BMEP |
| | |