| 2018-09-01 18:53:23 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. SEE FIRE COMMENTS ON PERMIT APPLICATION 18070442 |
| | REGARDING FIRE SPRINKLERS. |
| | |
| | THERE IS A LETTER REGARDING THE INTENT TO PROVIDE FIRE |
| | SPRINKLERS AND PERMIT DOCUMENTS, BUT THE DOCUMENTS WERE |
| | NOT PROVIDED; IN PARTICULAR, HYDRAULIC CALCS. IT IS NOT |
| | CLEAR IF EXISTING SERVICE IS SUFFICIENT TO PROVIDE |
| | SPRINKLERS TO THE PROPOSED STRUCTURE. |
| | |
| | IF FIRE DOES NOT REQUIRE THIS INFORMATION FOR THE |
| | FOUNDATION PERMIT, PLEASE ADVISE AND THIS COMMENT WILL |
| | BE REMOVED. |
| | |
| | 2. OK |
| | |
| | 3. FBC B CHAPTER 5, 6, 7, REVISE PLAN TO INCLUDE |
| | BUILDING TYPE, SQUARE FOOT AREA (GARAGE AND OFFICE |
| | SEPARATELY), SEPARATED OR NON SEPARATED OCCUPANCIES, |
| | NOTE THAT IT WILL BE A FIRE SPRINKLERED BUILDING, |
| | BUILDING HEIGHT, NUMBER OF STORIES. |
| | |
| | 4. INFORMATION GENERALLY REQUIRED FOR A FOUNDATION |
| | PERMIT: |
| | |
| | PERMIT APPLICATION WHICH STATES SCOPE (FOR FOUNDATION |
| | PERMIT, TYPICALLY FOOTINGS OR FOOTINGS AND SLAB) - |
| | APPLICATION IN PROJECTDOX IS BLANK |
| | GEOTECHNICAL REPORT - NOT SUBMITTED |
| | SURVEY DRAWING - OK |
| | STORM WATER POLLUTION PREVENTION PLAN - NOT SUBMITTED |
| | SITE PLAN - OK |
| | 1ST FLOOR ARCHITECTURAL PLAN - SUBMITTED BUT LACKS |
| | PROPOSED DFE (ELEVATION IN NAVD88) |
| | ARCHITECTURAL CROSS SECTION(S) OF THE BUILDING - NOT |
| | PROVIDED |
| | FOUNDATION PLAN - OK |
| | FOUNDATION DETAILS AND CROSS SECTIONS - OK |
| | STRUCTURAL ENGINEER'S GENERAL NOTES - OK |
| | UNDERGROUND PLUMBING PLAN - SUBMITTED, PENDING REVIEW |
| | ELECTRICAL PLAN SHOWING ANY UNDERGROUND CONDUIT - |
| | SUBMITTED, PENDING REVIEW |
| | ELECTRICAL GROUNDING TO STEEL DETAIL, IF APPLICABLE (OR |
| | EXPLAIN WHY THIS IS NOT APPLICABLE FOR THIS PROJECT). |
| | IF REQUIRED, A DETAIL IS REQUIRED AS A REVIEW, PERMIT, |
| | AND INSPECTION ARE REQUIRED PRIOR TO CONCRETE POUR - |
| | SUBMITTED, PENDING REVIEW |
| | PLAN SHOWING UNDERGROUND FIRE LINE - SUBMITTED, PENDING |
| | FIRE REVIEW (BLDG OK) |
| | THRESHOLD INSPECTION PLAN - NA |
| | SI OR RESIDENT INSPECTOR AGREEMENT (AS APPLICABLE) - |
| | RESIDENT INSPECTOR AGREEMENT REQUIRED (4000 PSI |
| | CONCRETE STRUCTURAL SLAB) |
| | THRESHOLD STATEMENT ON PLAN (IF APPLICABLE) - N/A, NOT |
| | THRESHOLD (RESIDENT) |
| | |
| | 5. SHEET S1, I WAS UNABLE TO LOCATE A SPECIFICATION FOR |
| | F5, EITHER REVISE PLAN TO INCLUDE OR DIRECT AS TO WHERE |
| | THIS CAN BE LOCATED. |
| | |
| | 6. FBC B 107.2.5, IT APPEARS THAT THIS IS LOCATED IN |
| | SFHA 7' NAVD88. S1 REFERS TO ARCHITECTURAL PAGES FOR |
| | ELEVATION; REVISE A1.1.1 TO INCLUDE (9' NAVD88 MINIMUM |
| | IS REQUIRED). |
| | |
| | 7. FBC B 107.3.5.1.1(1), PROVIDE A "CONSTRUCTION |
| | DOCUMENTS" ELEVATION CERTIFICATE. |
| | |
| | 8. THIS PERMIT WILL BE ISSUED WITH PROVISO: |
| | |
| | A. PRIOR TO CONCRETE POUR, A "BUILDING UNDER |
| | CONSTRUCTION" ELEVATION CERTIFICATE WILL BE REQUIRED. |
| | THIS MAY BE SENT VIA EMAIL FOR PRELIMINARY REVIEW. |
| | PRIOR TO FINAL INSPECTION BUT AFTER ALL MECHANICAL |
| | EQUIPMENT HAS BEEN INSTALLED AND FINAL GRADES |
| | COMPLETED, A "FINISHED CONSTRUCTION" ELEVATION |
| | CERTIFICATE WILL BE REQUIRED. THIS MAY BE SENT VIA |
| | EMAIL FOR PRELIMINARY REVIEW. |
| | |
| | B. THIS PERMIT IS ISSUED AT APPLICANT'S RISK PER FBC |
| | 105.13: |
| | |
| | PHASED PERMIT APPROVAL. AFTER SUBMITTAL OF THE |
| | APPROPRIATE CONSTRUCTION DOCUMENTS, THE BUILDING |
| | OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT FOR THE |
| | CONSTRUCT ION OF FOUNDATIONS OR ANY OTHER PART OF A |
| | BUILDING OR STRUCTURE BEFORE THE CONSTRUCTION DOCUMENTS |
| | FOR THE WHOLE BUILDING OR STRUCTURE HAVE BEEN |
| | SUBMITTED. THE HOLDER OF SUCH PERMIT FOR THE FOUNDATION |
| | OR OTHER PARTS OF A BUILDING OR STRUCTURE SHALL PROCEED |
| | AT THE HOLDER'S OWN RISK WITH THE BUILDING OPERATION |
| | AND WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE |
| | STRUCTURE WILL BE GRANTED. CORRECTIONS MAY BE REQUIRED |
| | TO MEET THE REQUIREMENTS OF THE TECHNICAL CODES. THIS |
| | PROVISION IS ONLY FOR THE FLORIDA BUILDING CODE. ALL |
| | OTHER AGENCY APPROVALS NECESSARY FOR CONSTRUCTION MUST |
| | BE SECURED PRIOR TO THIS PROVISION BEING APPLIED. |
| | |
| | C. SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE |
| | REQUIRED FOR THE FOLLOWING ITEMS AS APPLICABLE: |
| | LIGHT POLES/SITE LIGHTING |
| | FIRE ALARM |
| | FIRE SPRINKLER |
| | LOW VOLTAGE |
| | ACCESS |
| | LANDSCAPING |
| | IRRIGATION |
| | ALL OTHER ITEMS OTHER THAN BMEP |
| | |