| 2018-12-21 09:16:47 | PROVISO: |
| | FLOORING SUBMITTAL TO BE PROVIDED PRIOR TO FLLORING |
| | INSTALLATION. |
| | |
| | PLEASE ADVISE, WHAT FLOORING AND UNDERLAYMENT ARE |
| | PROPOSED? PLEASE ADVISE VIA EMAIL. IF THE UNDERLAYMENT |
| | PRODUCT PROPOSED IS NOT ONE FOR WHICH WE HAVE TEST |
| | REPORTS ON FILE, THE FOLLOWING REPORTS ARE REQUIRED: |
| | [FBC 1207.2]AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS AND SLEEPING UNITS FROM EACH |
| | OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A |
| | SOUND TRANSMISSION CLASS OF NOT LESS THAN 50, OR NOT |
| | LESS THAN 45 IF FIELD TESTED, FOR AIR-BORNE NOISE WHEN |
| | TESTED IN ACCORDANCE WITH ASTM E90. |
| | [FBC 1207.3]STRUCTURE-BORNE SOUND. FLOOR/CEILING |
| | ASSEMBLIES |
| | BETWEEN DWELLING UNITS AND SLEEPING UNITS OR BETWEEN A |
| | DWELLING |
| | UNIT OR SLEEPING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN |
| | THE STRUCTURE SHALL HAVE AN IMPACT INSULATION CLASS |
| | RATING OF |
| | NOT LESS THAN 50, OR NOT LESS THAN 45 IF FIELD TESTED, |
| | WHEN TESTED |
| | IN ACCORDANCE WITH ASTM E492. |
| | [FBC 603.1]ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723. |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER I |
| | [email protected] |
| | 561-805-6718 |
| | |