| 2018-10-17 14:12:23 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18081343 (8TH FLOOR) |
| | REVIEWED: OCTOBER 16, 2018 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER I |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC ENERGY = FBC ENERGY CONSERVATION |
| | |
| | 1. [FBC AMENDED 107.2.1]ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| | DESIGN. |
| | ALL SHEETS NEED GRAPHIC REPRESENTATION OF SEAL TO |
| | INCLUDE FLORIDA LICENSE NUMBER, NAME AND SIGNATURE OF |
| | ARCHITECT. |
| | ALSO, REMOVE THE NOTE FROM TITLE BLOCK THAT STATES |
| | ?PRELIMINARY DRAWINGS NOT TO USED FOR RECORDING, |
| | PERMITTING OR CONSTRUCTION? |
| | |
| | 2. [FBC AMENDED 107.2.1]WHEN RELOADING DRAWINGS MAKE |
| | SURE EACH SHEET IS DIGITALLY SIGNED. THIS WILL TAKE |
| | CARE OF THE SIGNATURE REVIEW THAT HAS FAILED 2ND ROUND |
| | REVIEW. |
| | |
| | 3. [FBC AMENDED 107.2.5]PROJECT DATA |
| | SPECIFY THE AFFECTED AREA ON EACH FLOOR AND THE |
| | OCCUPANCY OF THE AREAS. CONSTRUCTION TYPE, SPRINKLED OR |
| | NON, FINISH FIRE CLASSIFICATION. |
| | GENERAL FINISH NOTES STATE TO COMPLY WITH IBC 804 AND |
| | 804.3. PLEASE REMOVE THIS NOTE AND CHANGE TO FLORIDA |
| | BUILDING CODE REFERENCES. |
| | |
| | 4. [FBC AMENDED 107.2.5]ARE THERE ANY PENETRATIONS INTO |
| | EXISTING MAIN STRUCTURE DUE TO THIS WORK ON THE 8TH |
| | FLOOR? IF YES PLEASE PROVIDE DETAILS OF FIRE STOPPING. |
| | |
| | 5. [FBC AMENDED 107.2.5]SHEET I-180 HAS CALL OUTS IN |
| | THE LOUGE THAT REFER TO SHEET I-452. PLEASE INSERT THIS |
| | SHEET, OR CHANGE CALL OUTS TO THE PAGE WHERE THE |
| | ELEVATIONS CAN BE FOUND. |
| | |
| | 6. [FBC AMENDED 107.2.5]THE VALUE OF THIS WORK IS MORE |
| | THAN THE 5TH AND 6TH FLOOR BECAUSE IT INCLUDES THE |
| | RESIDENTIAL UNITS. IT IS UNCLEAR FROM THE DEMO PLANS |
| | WHAT IS BEING DONE IN THE UNITS. PLEASE PROVIDE |
| | DESCRIPTION OF WHAT IS BEING DONE TO THE RESIDENTIAL |
| | UNITS. IS IT JUST PAINT OR IS FLOORING INCLUDED. IF |
| | FLOORING IS BEING REPLACED PLEASE INCLUDE SUBMITTAL FOR |
| | IIC, STC AND FLAME SPREAD, OR INDICATE THAT IT WILL BE |
| | DEFERED. |
| | |
| | NOTE: |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |