| 2018-11-19 17:10:07 | 1ST REVIEW FBC-2014 MECHANICAL |
| | REVISION #18081315 |
| | MASTER #17040807 |
| | 11/19/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE- 2014 |
| | FBC M- FLORIDA MECHANICAL CODE- 2014 |
| | FBC EC- FLORIDA ENERGY CONSERVATION- 2014 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS- 2010 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS M2.1.1, M2.2.1, & M6.1: THE TOTAL AIRFLOW |
| | CFMS SHOWN ON THE 1ST AND 2ND FLOOR DUCT LAYOUT PLANS |
| | EXCEED THE CAPACITIES OF THE RTU'S 1 & 2, AND OF THE |
| | MAIN SUPPLY TRUNKS FOR EACH SYSTEM. FOR EXAMPLE, THE |
| | FIRST FLOOR PLAN (M2.1.1) SHOWS A TOTAL OF 26,600 CFMS |
| | OF SUPPLY AIR FOR RTU-1 WHICH HAS A MAXIMUM CAPACITY OF |
| | 10,118 CFMS. IN ADDITION THE 22X16 IS FAR UNDERSIZED TO |
| | SUPPLY 19,400 CFMS OF AIR. PLEASE REVIEW AND CORRECT- |
| | SECTION 603.1 FBC M |
| | |
| | 2) PROVIDE TWO COMPLETE SETS OF REVISED MECHANICAL |
| | DRAWINGS FOR REVIEW- ONLY ONE SET WAS SUBMITTED- |
| | SECTION 107.1 WPB. |
| | |
| | 3) PLEASE NOTE THAT COMMISSIONING OF THE MECHANICAL |
| | SYSTEMS IS REQUIRED FOR FINAL APPROVAL AND CO OF THE |
| | BUILDING- SECTION C408.2 FBC EC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |