Plan Review Notes
Plan Review Notes For Permit 18081315
Permit Number 18081315
Review Stop M
Sequence Number 2
Notes
Date Text
2018-11-19 17:10:071ST REVIEW FBC-2014 MECHANICAL
 REVISION #18081315
 MASTER #17040807
 11/19/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE- 2014
 FBC M- FLORIDA MECHANICAL CODE- 2014
 FBC EC- FLORIDA ENERGY CONSERVATION- 2014
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS- 2010
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS M2.1.1, M2.2.1, & M6.1: THE TOTAL AIRFLOW
 CFMS SHOWN ON THE 1ST AND 2ND FLOOR DUCT LAYOUT PLANS
 EXCEED THE CAPACITIES OF THE RTU'S 1 & 2, AND OF THE
 MAIN SUPPLY TRUNKS FOR EACH SYSTEM. FOR EXAMPLE, THE
 FIRST FLOOR PLAN (M2.1.1) SHOWS A TOTAL OF 26,600 CFMS
 OF SUPPLY AIR FOR RTU-1 WHICH HAS A MAXIMUM CAPACITY OF
 10,118 CFMS. IN ADDITION THE 22X16 IS FAR UNDERSIZED TO
 SUPPLY 19,400 CFMS OF AIR. PLEASE REVIEW AND CORRECT-
 SECTION 603.1 FBC M
  
 2) PROVIDE TWO COMPLETE SETS OF REVISED MECHANICAL
 DRAWINGS FOR REVIEW- ONLY ONE SET WAS SUBMITTED-
 SECTION 107.1 WPB.
  
 3) PLEASE NOTE THAT COMMISSIONING OF THE MECHANICAL
 SYSTEMS IS REQUIRED FOR FINAL APPROVAL AND CO OF THE
 BUILDING- SECTION C408.2 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  