| Notes |
| Date |
Text |
| 2018-08-31 15:28:04 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THE PROPOSED PROJECT INDICATES THE USE OF FLEX DROP | | | PIPING. THE EXISTING SYSTEM APPEARS TO A TYPICAL ARM | | | OVER. | | | | | | THERE IS NO HYDRAULIC CALCULATION SHEET SUBMITTED THAT | | | SHOWS THAT THE NEW FLEX DROPS WILL BE SUPPORTED BY THE | | | EXISTING SYSTEM DESIGN. | | | | | | PLEASE PROVIDE CALCULATION DETAIL OR SPECIFIC | | | INFORRMATION INDICATING THE REQUIRED FLOW AT EACH | | | SPRINKLER SHALL MEET THE REQUIREMENT OF THE DESIGN. | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|