| Plan Review Notes For Permit 18081283 |
| Permit Number |
18081283 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-09-14 14:05:53 | 1.)THE PROPOSED PROJECT INDICATES THE USE OF FLEX DROP | | | PIPING. THE EXISTING SYSTEM APPEARS TO A TYPICAL ARM | | | OVER. | | | FLEX DROPS TYPICALLY HAVE A HIGHER FRICTION LOSS THAN | | | THE DESIGNED ARM OVER SYSTEM. | | | THERE IS NO HYDRAULIC CALCULATION SHEET SUBMITTED THAT | | | SHOWS THAT THE NEW FLEX DROPS WILL BE SUPPORTED BY THE | | | EXISTING SYSTEM DESIGN TO PROVIDE THE REQUIRED WATER | | | FLOW. | | | PLEASE PROVIDE CALCULATIONS DETAILS OR USE THE SAME | | | TYPE OF ARM OVER THAT MATCHES THE EXISTING SYSTEM | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. |
|