| 2018-09-07 05:53:18 | 1) THE EXISTING GAS PLANS ON FILE IN CITY RECORDS FOR | | | THIS ADDRESS SHOW A 400,000 BTU POOL HEATER ON THE | | | EXISTING SYSTEM BUT THE NEW GAS PLANS DO NOT SHOW THIS | | | POOL HEATER. CLARIFY. THE ADDED POOL HEATER WILL CHANGE | | | THE TOTAL BTU LOAD TO 888,000 BTU'S. | | | 2) THE LOCATION OF THE GENERATOR EXHAUSST SHALL BE A | | | MINIMUM OF 10 FEET FROM ANY BUILDING OPENINGS INCLUDING | | | SOFFIT VENTS. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|