Plan Review Notes
Plan Review Notes For Permit 18081269
Permit Number 18081269
Review Stop P
Sequence Number 1
Notes
Date Text
2018-08-27 13:51:4508/27/2018 1ST PLUMBING/BACKFLOW REVIEW **DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THIS BACKFLOW IS NOT A LEAD-FREE DEVICE WHICH IS
 REQUIRED BY THE CITY OF WEST PALM BEACH UTILITY
 DEPARTMENT. YOU CAN REFER TO THEIR CROSS CONNECTION
 MANUAL IN THE CITY WEB SITE HTTP://WPB.ORG/DEPARTMENTS/
 PUBLIC-UTILITIES/FORMS-PUBLICATIONS/BACKFLOW-CROSS-CONN
 ECTION-CONTROL-MANUAL FOR MORE INFORMATION. THE 975XL
 WATKINS MODEL IS NOT LEAD-FREE AS THE 975XL2 IS SO
 PLEASE RESUBMIT SPECS FOR IT.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved