| 2019-01-02 13:11:50 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 5TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | 2ND REVIEW: DENIED |
| | PLUMBING COMMENTS |
| | 1. RE: PLAN SHEET 1A-101 DATED 8/16/2018; EXISTING |
| | SHEET IS REDLINED. COMMENTS ARE NO LONGER APPLICABLE. |
| | REPLACE WITH CLEAN SIGNED AND SEALED. |
| | 2. OCCUPANCY IS BUSINESS WITH OCCUPANT LOAD OF 262. |
| | THERE ARE NO DRINKING FOUNTAINS SHOWN ON THE PLAN. SHOW |
| | EXISTING AND, IF REQUIRED, ADD NEW DRINKING FOUNTAINS |
| | COMPLYING WITH FBC PL TABLE 403.1, SECTION 410 AND FBC |
| | ACC SECTION 211, 307 AND 602. REVISE PLUMBING PLANS AS |
| | REQUIRED. |
| | 3. RE: PLAN SHEET P2.1 AND P5.1; PER CITY OF WPB |
| | UTILITIES DEPARTMENT, ALL KITCHEN EQUIPMENT AND |
| | FIXTURES SHALL DISCHARGE INTO GREASY WASTE DRAINAGE |
| | INTO THE GREASE INTERCEPTOR. REVISE PLUMBING PLANS TO |
| | SHOW COMPLIANCE. CONTACT MR. JEFFERY ODOMS, CITY OF WPB |
| | UTILITIES AT 561-822-2172 OR EMAIL [email protected] WITH |
| | ANY QUESTION OR CONCERN. |
| | 4. PER WPB FBC 107.2.1, PROVIDE CALCULATIONS FOR NEW |
| | AND EXISTING EQUIPMENT AND FIXTURES DISCHARGING TO THE |
| | GREASE INTERCEPTOR AND PROVIDE CAPACITY OF EXISTING |
| | INTERCEPTOR SHOWING THAT IT WILL ACCOMMODATE THE |
| | INCREASED LOAD. |
| | 5. PLAN SHEET E5.1 INDICATES A SEPARATE REFRIGERATOR |
| | AND SEPARATE ICE MACHINE. P5.1 INDICATES A REFRIGERATOR |
| | WITH ICE MAKER. PLEASE CLARIFY PER WPB FBC 107.2.1. |
| | 6. PLAN SHEET E5.1 DOES NOT SEEM TO INDICATE A |
| | DISHWASHER. P5.1 INDICATES A DISHWASHER. PLEASE CLARIFY |
| | AND SHOW LOCATION ON THE FLOOR PLAN AND WATER RISER |
| | DIAGRAM PER WPB FBC 107.2.1. |
| | 7. PER WPB FBC 107.2.1, PROVIDE SCHEDULE AND DETAIL FOR |
| | FIXTURE TAG SK-3 |
| | 8. THE WATER RISER DIAGRAM INDICATES BACKFLOW |
| | PREVENTERS FOR COFFEE MAKERS, FILTERS, ICE MAKER WATER |
| | SUPPLY LINES. TYPICAL PLUMBING FIXTURE CONNECTION |
| | SCHEDULE CALLS OUT VACUUM BREAKERS. BE SPECIFIC; |
| | SPECIFY BACKFLOW PREVENTER DEVICES LISTING THE ASSE, |
| | CSA OR AWWA STANDARD WHICH IS APPLICABLE TO THAT DEVICE |
| | PER WPB FBC 107.2.1. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | |