| 2018-09-28 12:51:52 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND |
| | SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE |
| | ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H); |
| | 471.025; WPB FBC 107.2.1, 107.3.5 |
| | |
| | AN ENGINEERED ELECTRICAL CEILING PLAN WAS SUBMITTED FOR |
| | 2ND FL BATHROOMS. ONLY E0.1 AND E2.1 PAGES SUBMITTED. |
| | APPEARS TO BE MISSING PAGES. ARCHITECTUAL PLAN SHOWS |
| | ELECTRICAL WORK THROUGHOUT THE 1ST FLOOR AND 2ND FLOOR, |
| | NOT JUST CORRIDORS, BUT THE PERMIT APPLICATION ONLY |
| | SAYS "INTERIOR CORRIDOR ALTERATIONS". SUBMIT A COMPLETE |
| | AND ACCURATE ELECTRICAL PLAN INCLUDING ALL WORK TO BE |
| | PERFORMED WITH LOAD CALCULATIONS FOR REVIEW. |
| | |
| | 2. PROVIDE SUBMITTALS FOR PRODUCT APPROVAL (UL OR NRTL |
| | LISTINGS) FOR LIGHT FIXTURES. NEC 110.3 |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WPB |