| Plan Review Notes For Permit 18081242 |
| Permit Number |
18081242 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-08-28 10:15:51 | PERMIT # 18081242 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | APPROVED PROVISO: | | | | | | 1) THIS APPROVAL IS FOR THE FIRE SPRINKLER SYSTEM | | | WITHIN THE HOTEL, ONLY. SEPARATE PLANS AND PERMITS | | | NEEDED FOR PRIVATE UNDERGROUND FIRE LINE AND FIRE | | | HYDRANTS. | | | | | | 2) PROVIDE CHAIN WITH LOCK AND TAMPER SWITCHES FOR | | | SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN | | | POSITION. | | | | | | 3) PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT | | | CONNECTION. | | | | | | 4) PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE | | | DEPARTMENT CONNECTION. | | | | | | | | | SUE ELLEN CALDERON | | | ASSISTANT FIRE MARSHAL | | | [email protected] | | | |
|