| 2018-09-11 12:39:20 | RESIDENTIAL (R3) SHUTTERS, SECOND BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | ORIGINAL COMMENT: |
| | 1- ACCORDING TO SEC. R301.2.1.4 FBC-RESIDENTIAL THIS |
| | BUILDING IS LOCATED IN EXPOSURE "D" NOT EXPOSURE "C". |
| | REVISE ENGINEERING CALCULATIONS SUBMITTED. |
| | |
| | RESPONSE: |
| | ENGINEER CALCULATIONS WERE REVISED BUT INSTALLATION |
| | SCHEDULE WAS NOT REVISED. THE DESIGN PRESSURES DON'T |
| | MATCH. REVISE AS REQUIRED TO MATCH. SEC. R301.1 |
| | FBC-RESIDENTIAL. |
| | |
| | ORIGINAL COMMENT: |
| | 2- REVISE ANCHOR SPACING AS REQUIRED BY THE REVISED |
| | ENGINEERING CALCULATIONS. SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | ANCHOR SPACING WAS NOT REVISED. THE ANCHOR SPACING USED |
| | ON THE FIRST SUBMITTAL WAS THE SAME FOR CONCRETE AND |
| | CONCRETE BLOCK INSTALLATIONS. THE REVISED DESIGN |
| | PRESSURES REQUIRE A DIFFERENT ANCHOR SPACING FOR |
| | CONCRETE AND CONCRETE BLOCK INSTALLATION. REVISE ANCHOR |
| | SPACING AS REQUIRED. SEC. R301.1 FBC-RESIDENTIAL. |
| | NOTE: TYPICALLY CONCRETE BLOCK HOUSES HAVE A PRECAST OR |
| | CONCRETE POURED BEAM AND THE BOTTOM IS CONCRETE BLOCK |
| | (FILLED OR NOT FILLED IS STILL CONCRETE BLOCK). REVISE |
| | ANCHOR SPACING FOR CONCRETE OR CONCRETE BLOCK |
| | INSTALLATION OR PROVIDE PROOF THAT OPENING SILL HAS A |
| | 3192 PSI CONCRETE STRENGTH AS REQUIRED ON GENERAL, NOTE |
| | #6 ON SHEET 1 OF 10 OF SHUTTERS PRODUCT APPROVAL |
| | SUBMITTED. |
| | |
| | ORIGINAL COMMENT: |
| | 3- ACCORDING TO NOTE #3 ON SHEET 2 OF 10 OF STORM |
| | PANELS DRAWING 17-089 SUBMITTED THE MINIMUM PANEL |
| | LENGTH IS 48 INCHES. THERE ARE SOME PANELS THAT ARE |
| | LESS THAN 48 INCHES LONG. REVISE AS REQUIRED. SEC. |
| | R301.1 FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. INSTALLATION SCHEDULE |
| | SUBMITTED WAS NOT REVISED. REVISE THE SHUTTER SPAN AS |
| | REQUIRED. SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | |