| 2018-09-12 12:04:21 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18081226 |
| | 9/12/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE EXHAUST VENTILATION CALCULATIONS FOR THE |
| | MANICURE AND PEDICURE STATIONS, AND THE BEAUTY SALON |
| | AREA- SEE TABLE 403.3.1.1 FBC M. PLEASE NOTE THAT THE |
| | PLAN DOES NOT APPEAR TO SHOW EXHAUST VENTILATION IN THE |
| | BEAUTY SALON AREA. |
| | |
| | 2) PROVIDE AIR BALANCE CALCULATIONS AND A SEQUENCE OF |
| | OPERATION FOR THE EXHAUST SYSTEMS- SECTION 501.4 FBC M. |
| | PLEASE NOTE THAT INSTALLATION OF AN ERV MAY BE REQUIRED |
| | PER SECTION C403.2.7 FBC EC. |
| | |
| | 3) PROVIDE A DETAIL THAT INDICATES HOW THE FUMES AT THE |
| | PEDICURE CHAIRS ARE BEING CAPTURED AT THEIR SOURCES- |
| | TABLE 403.3.1.1 FOOTNOTE H FBC M |
| | |
| | 4) M-1: THE PLAN APPEARS TO SHOW RECIRCULATION OF THE |
| | AIR FROM THE NAIL AND BEAUTY SALON IINTO THE RECEPTION |
| | AREA, THE MASSAGE AND WAX ROOMS, AND THE BACK OF HOUSE |
| | AREAS WHICH IS PROHIBITED PER TABLE 403.3.1.1 FOOTNOTE |
| | B FBC M. |
| | |
| | 5) M-1: PROVIDE A DUCT SMOKE DETECTOR IN THE SUPPLY |
| | SIDE OF RTU-5- SECTION 606.2.1 FBC M. |
| | |
| | 6) M-1: PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE NEW |
| | AHU-1- SECTION 307 FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |