| 2018-09-24 08:57:36 | BUILDING PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER, PX3169 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 2ND REVIEW |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. COMMENT # 4 FROM 1ST REVIEW HAS NOT BEEN ADDRESSED. |
| | SEE BELOW. |
| | 4) SUBMIT TWO SETS OF THE MANUFACTURER'S SPECIFICATIONS |
| | AND INSTALLATION INSTRUCTIONS FOR THE ELEVATOR. PROVIDE |
| | DOCUMENTATION THE ELEVATOR COMPLIES WITH ASME A17.1/CSA |
| | B44. FBC 107.2.1 & FBC-R321.1. |
| | |
| | 2. SECOND FLOOR PLAN INDICATES A PARAPIT WALL ABOVE |
| | ELEVATOR HOISTWAY. ROOF FRAMING PLAN APPROVED UNDER |
| | MPERMIT # 17110548 INDICATES A STANDINJG SEAM METAL |
| | ROOF IN THIS AREA. PROVIDE A PLAN AND DETAIL FOR THE |
| | RECONFIGURATION OF THIS ROOF LINE. IF A FLOOT ROOF WILL |
| | BE INSTALLED, PROVIDE PRODUCT APPROVALS FOR FLAT ROOF |
| | SYSTEM. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE |
| | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. |
| | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | SPECIFICALLY, PROVIDE ROOFING SUBMITTALS. |
| | |
| | 3. SIGNATURE AND SEAL OF DESIGN PROFESSIONALS ARE |
| | COPIES. ORIGINAL SIGNATURE AND SEALS ARE REQUIRED. |
| | PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND |
| | SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE, |
| | DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE |
| | 61G15-23.001. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED AND MARK VOID. |
| | |
| | |
| | |
| | |
| | |