| Plan Review Notes For Permit 18081220 |
| Permit Number |
18081220 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-08-28 18:25:02 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE PLANS ON FILE FOR PERMIT #17070538 ARE FOR | | | REMODELING A TWO STORY GARAGE/APARTMENT. THERE IS NO | | | ELEVATOR SHOWN ON ANY OF THE PLANS THAT ARE FILE WITH | | | THE BUILDING DEPARTMENT. IF YOU HAVE AN APPROVED SET OF | | | PLANS WITH THE CITY BUILDING DEPARTMENT STAMPS, PLEASE | | | BRING THEM IN SO THAT WE MAY MAKE A COPY FOR OUR | | | RECORDS. | | | | | | 2) SUBMIT TWO SETS OF FLOOR PLANS SHOWING THE | | | DIMENSIONS AND LOCATION OF OF THE ELEVATOR HOISTWAY AND | | | THE ELEVATOR EQUIPMENT ROOM. FBC 107.2.1 | | | | | | 3) PROVIDE FRAMING DETAILS OF THE ELEVATOR HOISTWAY AND | | | ANY SPECIAL FRAMING/BLOCKING REQUIREMENTS. FBC 107.2.1 | | | | | | 4) SUBMIT TWO SETS OF THE MANUFACTURER'S SPECIFICATIONS | | | AND INSTALLATION INSTRUCTIONS FOR THE ELEVATOR. PROVIDE | | | DOCUMENTATION THE ELEVATOR COMPLIES WITH ASME A17.1/CSA | | | B44. FBC 107.2.1 & FBC-R321.1 | | | | | | 3) |
|