2018-09-19 14:59:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW:
 PERMIT 18081189
 PLUMBING COMMENTS: DENIED
  
 1. SKETCHES PROVIDED BY HARRY BARBER PLUMBING, INC. DO
 NOT REFLECT PLAN LAYOUT. IS ONE OF THE EXISTING TOILET
 ROOMS TO BE RECONFIGURED. PLEASE CLARIFY AND IF SO,
 PLEASE NOTE ON PLANS SHOWING EXISTING, THEN PROPOSED.
 2. THE PROJECT TITLE BLOCK ON PLAN PAGES 4 AND 5 ARE
 NOT THE SAME AS PAGES 1,2 AND 3. PLEASE CLARIFY.
 3. PROVIDE DESIGN OCCUPANT LOAD CALCULATIONS SO THAT
 MINIMUM FIXTURE REQUIREMENTS MAY BE DETERMINED. FBC
 SECTION 1004
 3. PROVIDE ON PLUMBING PLAN IN ACCORDANCE WITH WPB FBC
 107.3.5.1.3, THE FOLLOWING:
 A. MINIMUM PLUMBING FACILITIES PER FBC PL 403.1 AND
 TABLE 403.1. (SEE NOTE 3)
  *PER FBC PL TABLE 403.1; MERCANTILE, FURNISH ONE (1)
 DRINKING FOUNTAIN WHICH COMPLIES WITH FBC ACC 602,
 211.2 NOTE EXCEPTION IN FBC PL 410.
  *PER FBC PL TABLE 403.1; MERCANTILE, FURNISH ONE (1)
 SERVICE SINK.
 B. WATER SUPPLY PIPING PLAN LAYOUT AND RISER DIAGRAM
 NOTING THE WORK TO BE DONE INTEGRATE WITH THE EXISTING.
 CLOUD NEW WORK.
 C. SANITARY PLAN LAYOUT AND RISER DIAGRAM NOTING THE
 WORK TO BE DONE INTEGRATE WITH THE EXISTING. CLOUD NEW
 WORK.
 D. PROVIDE SCHEDULE FOR INSTA HOT WATER HEATER. IF NOT
 TANKLESS THEN PROVIDE FOR T&P RELIEF, DRAIN PAN AND PAN
 PER FBC PL SECTION 504. INSURE THAT IT WILL MEET THE
 HOT WATER DEMAND OF FIXTURES SERVICED.
 E. PER FBC PL 416.5, PROVIDE TEMPERED WATER FROM
 LAVATORIES AND GROUP WASH FIXTURES LOCATED IN PUBLIC
 TOILET FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3.
 4. PER WPB FBC, PLAN (EACH SHEET OF BOTH COPIES) IS
 REQUIRED TO BEAR THE NAME AND BE SIGNED AND SEALED BY
 THE PERSON RESPONSIBLE FOR THE DESIGN. THIS PERSON MUST
 BE A LICENSED DESIGN PROFESSIONAL OR THE PLUMBING
 CONTRACTOR QUALIFIER. PROVIDE CORRECTION. WPB FBC
 107.1, 107.2; FS 471, 481
 5. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. CONTINGENT UPON REVIEW BY BUILDING, CONSTRUCTION
 VALUE IS YET TO BE DETERMINED. WPB FBC 109 UPON
 DETERMINATION OF SAID VALUE, ACCESSIBILITY FOR UP TO
 20% OF SAID VALUE SHALL BE APPLIED UPGRADE THE
 ACCESSIBILITY REQUIREMENTS AS NOTED IN FAC 202.4.1.
 6. PLANS SHALL PROVIDE INFORMATION INCLUDING DIMENSIONS
 AND DETAILS SHOWING COMPLIANCE INCLUDING SHOWING AND
 IDENTIFYING ACCESSIBLE BATHS PER WPB FBC 107.3.5.1(10)
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID".
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6715
  