Plan Review Notes
Plan Review Notes For Permit 18081189
Permit Number 18081189
Review Stop M
Sequence Number 1
Notes
Date Text
2018-09-18 07:36:101ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18081189
 9/18/18
  
 CODES IN EFFECT:
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO SECTION 809.2 FBC-17 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3.1 FBC-17 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 2) SHEET 3: SHOW THE LOCATIONS OF THE AIR HANDLERS AND
 PROVIDE BASIC INFORMATION- MAKES AND MODELS, COOLING
 AND HEATING CAPACITIES.
  
 3) SHEET 3: INDICATE HOW THE RETURN AIR SYSTEM WILL
 FUNCTION. NO DETAILS ARE PROVIDED.
  
 2) SHEET 3: PROVIDE AN AIR DEVICE SCHEDULE AND A DETAIL
 SHOWING HOW THE NEW SOFFITS AND AC VENTS WILL BE
 CONSTRUCTED AND SUPPORTED.
  
 3) SHEET 3: PROVIDE THE SUPPLY CFMS AT EACH SOFFIT VENT
 AND RETURN CFMS AT EACH GRILL OR VENT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
 HTTPS://WWW.SURVEYMONKEY.COM/R/WESTPALMBEACHCONSTRUCTIO
 NSERVICES
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved