| 2018-09-18 07:36:10 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18081189 |
| | 9/18/18 |
| | |
| | CODES IN EFFECT: |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) REFER TO SECTION 809.2 FBC-17 EXISTING BUILDING CODE |
| | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL |
| | ROOMS AND SPACES PER TABLE 403.3.1 FBC-17 MECHANICAL. |
| | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND |
| | PROVIDED CFMS OF OUTDOOR AIR. |
| | |
| | 2) SHEET 3: SHOW THE LOCATIONS OF THE AIR HANDLERS AND |
| | PROVIDE BASIC INFORMATION- MAKES AND MODELS, COOLING |
| | AND HEATING CAPACITIES. |
| | |
| | 3) SHEET 3: INDICATE HOW THE RETURN AIR SYSTEM WILL |
| | FUNCTION. NO DETAILS ARE PROVIDED. |
| | |
| | 2) SHEET 3: PROVIDE AN AIR DEVICE SCHEDULE AND A DETAIL |
| | SHOWING HOW THE NEW SOFFITS AND AC VENTS WILL BE |
| | CONSTRUCTED AND SUPPORTED. |
| | |
| | 3) SHEET 3: PROVIDE THE SUPPLY CFMS AT EACH SOFFIT VENT |
| | AND RETURN CFMS AT EACH GRILL OR VENT. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |