| 2018-08-25 12:19:48 | PLAN REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT TWO SETS OF A KEY PLAN AND AN ACCORDION | | | SHUTTER INSTALLATION SCHEDULE THAT LISTS EACH OF THE | | | EIGHT OPENINGS. SPECIFY THE OPENING SIZE, THE WIND | | | PRESSURES FOR EACH OPENING, TYPE OF ANCHOR, ANCHOR | | | SPACING, EDGE DISTANCE, PANEL LENGTH, PANEL SPAN, | | | SEPARATION DISTANCE FROM PANEL TO GLASS AND THE | | | APPLICABLE SECTION NUMBER FROM THE INSTALLATION | | | DRAWINGS. I HAVE INCLUDED A LINK TO THE CONSTRUCTION | | | SERVICES DEPARTMENT SITE THAT HAS MANY OF THE RELATED | | | FORMS INCLUDING THE SCHEDULE FOR INSTALLATION OF | | | OPENING PROTECTIVE DEVICES. | | | HTTP://WPB.ORG/DEVELOPMENT/FORMS-AND-PUBLICATIONS/ | | | |
|