| 2018-10-09 12:06:11 | 1ST REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. A MIN OF 1 URINAL SHALL COMPLY WITH FBC ACC 213.3.3 |
| | AND 605 |
| | |
| | 2. WHERE TOILET COMPARTMENTS ARE PROVIDED, AT LEAST ONE |
| | TOILET COMPARTMENT SHALL COMPLY WITH 604.8.1. IN |
| | ADDITION TO THE COMPARTMENT REQUIRED TO COMPLY WITH |
| | 604.8.1, AT LEAST ONE COMPARTMENT SHALL COMPLY WITH |
| | 604.8.2 WHERE SIX OR MORE TOILET COMPARTMENTS ARE |
| | PROVIDED, OR WHERE THE COMBINATION OF URINALS AND WATER |
| | CLOSETS TOTALS SIX OR MORE FIXTURES. THE EXISTING |
| | TOILET STALL MAY COMPLY WITH 604.8.1 PLEASE PROVIDE |
| | ENLARGED DETAIL SHOWING ALL REQUIRED DIMENSIONS. PER |
| | FBC ACC 213.3.1 |
| | |
| | 3. PLEASE PROVIDE A WATER AND SANITARY ISOMETRIC |
| | DRAWING. PER WPB AMEND TO FBC 107.3.5.1.3(13) |
| | |
| | 4. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES |
| | AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET |
| | FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND |
| | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| | CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5 |
| | |
| | 5. PLEASE PROVIDE A PLUMBING FIXTURE COUNT BREAK DOWN |
| | WIT NEW OCCUPANT LOAD. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |