2018-09-28 11:55:171ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18081131
 9/28/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS G1.0 & M2.1: ACCORDING TO THE CODE DATA
 LISTED ON G1.0, THE VENTILATION SYSTEM FOR THE LAB HAS
 BEEN DESIGNED IN COMPLAINCE WITH FLORIDA MECHANICAL
 CODE SIXTH EDITION (2017). REFER TO TABLE 403.3.1.1 AND
 PROVIDE AN EXHAUST SYSTEM FOR THE LAB BASED ON 1.0 CFMS
 PER SQ. FT. AND OUTDOOR AIR AT A RATE BASED ON AN
 OCCUPANT DENSITY OF 25 PERSONS PER 1000 SQ. FT. AT 10
 CFMS PER PERSON + 0.18 CFMS PER SQ. FT. REVISE THE
 PLANS ACCORDINGLY AND PROVIDE VENTILATION CALCULATIONS.
 ADVISORY: PLEASE SEE TABLE 7-1 DESIGN PARAMETERS ASHRAE
 170. AS INDICATED IN THE TABLE, LABORATORIES REQUIRE
 NEGATIVE PRESSURE, AND DEPENDING ON THE TYPE OF
 LABORATORY, ALSO REQUIRE ALL ROOM AIR TO BE EXHAUSTED
 DIRECTLY TO THE OUTDOORS.
  
 2) SHEET M2.1: THE PLAN INDICATES RECIRCULATION OF AIR
 FROM THE LAB INTO ADJACENT SPACES WHICH IS LIMITED TO
 10 PERCENT OF THE AIR FROM THE LAB- SEE TABLE 403.3.1.1
 FOOTNOTE G AND PROVIDE AIR BALANCE CALCULATIONS.
  
 3) M2.1, M2.2, & M6.1: RE AND SE ARE NOT SHOWN IN THE
 AIR DEVICE SCHEDULE.
  
 4) M2.3: SUBMIT A FL. PRODUCT APPROVAL AND A MIAMI-DADE
 NOA FOR THE NEW LOUVER- RULE 9N-3 FAC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  