| 2018-09-19 12:53:02 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 1ST REVIEW: |
| | PERMIT 18081117 |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. PROVIDE NOTE D/W AND REF ICE LINE STATING "WATER |
| | HAMMER ARRESTOR TO BE INSTALLED IN ACCORDANCE WITH FBC |
| | RES P2903.5" |
| | 2. PROVIDE NOTE AT SHOWER STATING "SHOWER CONTROL |
| | VALVE(S) SHALL BE PRESSURE BALANCED PB,THERMOSTATIC |
| | MIXING (TM) OR COMBINATION PB/TM VALVE TYPES WITH HIGH |
| | TEMPERATURE LIMITING STOP." FBC RES P2708.4 |
| | 3. WILL THERE BE A HAND HELD SHOWER? PLEASE CLARIFY ON |
| | PLAN. IF SO, PROVIDE NOTE STATING "HAND HELD SHOWER |
| | REQUIRES AN ATMOSPHERIC VACUUM BREAKER AT SHOWER ARM |
| | OUTLET." FBC RES P2708.5 |
| | 4. THE NOTE CONCERNING THE "NEW RAINSHOWER HEAD WITH |
| | SEPARATE CONTROLS" INDICATES THAT THERE WILL BE NEW |
| | TILE WORK. IF SO, SUCH NEW WORK SHOULD BE INDICATED ON |
| | THE PLANS. ADDITIONALLY IF THE SHOWER FLOOR IS INVOLVED |
| | A CURRENT CODE COMPLIANT SHOWER PAN MAY BE REQUIRED. |
| | |
| | |
| | NOTE OF INTEREST |
| | RE: LAVATORY DRAIN; ONE SINGLE TRAP SERVICING TWO |
| | LAVATORIES AS NOTED AND SHOWN IS PERMITTED PER FBC RES |
| | P3201.6 SO LONG AS THE DISTANCE BETWEEN THE TWO OUTLETS |
| | DOES NOT EXCEED 30". |
| | HOWEVER, FOR A FEASIBLE ALTERNATIVE INSTALLATION, |
| | PLEASE REFER TO FBC RES P3107.2 COMMON VENT, ALLOWING |
| | FOR INSTALLATION OF INDIVIDUAL TRAP FOR EACH LAV AND |
| | CONNECT FIXTURE DRAINS TO SINGLE BRANCH STUBBED OUT |
| | UNDER COUNTER. IF THIS METHOD IS TO BE USED, THEN NOTE |
| | AND SHOW ON PLAN. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID". |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6715 |
| | |