| 2018-09-04 16:43:48 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | 2/0'S ONLY APPLY WHEN THE ENTIRE LOAD IS FED FROM ONE | | | SET OF SERVICE ENTRANCE CONDUCTORS/FEEDERS. 3/0 ARE | | | REQUIRED FOR THE TWO 200A PANELS. | | | | | | E3603.1.2UNGROUNDED FEEDER CONDUCTORS. | | | FOR A FEEDER RATED AT 100 THROUGH 400 AMPERES, THE | | | FEEDER CONDUCTORS SUPPLYING THE ENTIRE LOAD ASSOCIATED | | | WITH A ONE-FAMILY DWELLING, OR THE | | | FEEDER CONDUCTORS SUPPLYING THE ENTIRE LOAD ASSOCIATED | | | WITH AN INDIVIDUAL DWELLING UNIT IN A TWO-FAMILY | | | DWELLING, SHALL HAVE AN AMPACITY OF NOT | | | LESS THAN 83 PERCENT OF THE FEEDER RATING. |
|