2018-09-18 12:05:41** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) ELEMENTS IN THE PHOTOMETRIC PLAN DOES NOT MATCH THE
 IMPROVEMENTS TO THE BELMART PLAZA SITE. PLEASE ADDRESS.
 [8/30 COMMENT NOT ADDRESSED]
  
 2.) LOCATION OF THE PROPOSED LIGHT FIXTURES SEEM TO
 CONFLICT WITH APPROVED AND INSTALLED LANDSCAPING ON THE
 PROPERTY. LANDSCAPING CANNOT BE REMOVED AND/OR
 RELOCATED WITHOUT THE APPROVAL OF THE CITY'S LANDSCAPE
 PLANNER BY A SEPARATE LANDSCAPE PERMIT. PLEASE ADDRESS.
 [8/30 COMMENT NOT ADDRESSED]
  
  
 NOTES:
  
 * REFERENCE: ISPR 14-01
  
 * REVISION MAY RESULT IN ADDITIONAL COMMENTS.
  
 * ZONE: GC
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * SPOKE TO PAUL GANGLOFF OF RIVERSIDE ELECTRIC ON
 9/18/18 AND EXPLAINED WHY THE PERMIT HAD FAILED. LATEST
 APPROVED PLAN SENT TO MR. GANGLOFF TO FORWARD TO THE
 ELECTRICAL ENGINEER, AS SUBMITTED PLANS ARE OUTDATED
 AND DO NOT MATCH WHAT IS EXISTING ON PROPERTY.
  