| Plan Review Notes For Permit 18081075 |
| Permit Number |
18081075 |
|
| Review Stop |
Z |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-09-18 12:05:41 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) ELEMENTS IN THE PHOTOMETRIC PLAN DOES NOT MATCH THE | | | IMPROVEMENTS TO THE BELMART PLAZA SITE. PLEASE ADDRESS. | | | [8/30 COMMENT NOT ADDRESSED] | | | | | | 2.) LOCATION OF THE PROPOSED LIGHT FIXTURES SEEM TO | | | CONFLICT WITH APPROVED AND INSTALLED LANDSCAPING ON THE | | | PROPERTY. LANDSCAPING CANNOT BE REMOVED AND/OR | | | RELOCATED WITHOUT THE APPROVAL OF THE CITY'S LANDSCAPE | | | PLANNER BY A SEPARATE LANDSCAPE PERMIT. PLEASE ADDRESS. | | | [8/30 COMMENT NOT ADDRESSED] | | | | | | | | | NOTES: | | | | | | * REFERENCE: ISPR 14-01 | | | | | | * REVISION MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | * ZONE: GC | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | | | | * SPOKE TO PAUL GANGLOFF OF RIVERSIDE ELECTRIC ON | | | 9/18/18 AND EXPLAINED WHY THE PERMIT HAD FAILED. LATEST | | | APPROVED PLAN SENT TO MR. GANGLOFF TO FORWARD TO THE | | | ELECTRICAL ENGINEER, AS SUBMITTED PLANS ARE OUTDATED | | | AND DO NOT MATCH WHAT IS EXISTING ON PROPERTY. | | | |
|