| Plan Review Notes For Permit 18081075 |
| Permit Number |
18081075 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-09-06 14:56:07 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | VALUE TOO LOW FOR PROPOSED WORK, SUBMIT SIGNED | | | CONTRACT. | | | | | | WIND LOADS NEED TO BE SUBMITTED, AND SIGNED AND SEALED | | | DRAWINGS FOR POLE WIH FIXURES. | | | | | | SHOW LIGHTING CONTROL FOR LIGHTS (PHOTCELL, TIME | | | CLOCK?) | | | | | | EXTERIOR LIGHTING CONTROLS. LIGHTING NOT DESIGNATED FOR | | | DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY | | | EITHER A COMBINATION OF A PHOTOSENSOR AND A TIME | | | SWITCH, OR AN ASTRONOMICAL TIME SWITCH. LIGHTING | | | DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE | | | CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR | | | PHOTOSENSOR. | | | ALL TIME SWITCHES SHALL BE CAPABLE OF RETAINING | | | PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER | | | FOR A PERIOD OF AT LEAST 10 HOURS. FBC CE 405.2.4 | | | | | | WALL PACKS TWO SHOWN NEED TO SUBMIT CUT SHEETS TYPE | | | VSC-1 AND HOW THEY MOUNT | | | | | | VSF-1 NEED TO SHOW LOCATION OF ALL 12 ON PLANS DRAWINGS | | | ONLY SHOW 2, PLUS SHOW HOW THEY MOUNT. | | | | | | WILL SUBMIT TO BUILDING WHEN ALL WIND LOADS AND CUT | | | SHEETS ARE SUBMITTED. |
|