Plan Review Notes
Plan Review Notes For Permit 18081075
Permit Number 18081075
Review Stop E
Sequence Number 1
Notes
Date Text
2018-09-06 14:56:07FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 VALUE TOO LOW FOR PROPOSED WORK, SUBMIT SIGNED
 CONTRACT.
  
 WIND LOADS NEED TO BE SUBMITTED, AND SIGNED AND SEALED
 DRAWINGS FOR POLE WIH FIXURES.
  
 SHOW LIGHTING CONTROL FOR LIGHTS (PHOTCELL, TIME
 CLOCK?)
  
 EXTERIOR LIGHTING CONTROLS. LIGHTING NOT DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY
 EITHER A COMBINATION OF A PHOTOSENSOR AND A TIME
 SWITCH, OR AN ASTRONOMICAL TIME SWITCH. LIGHTING
 DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE
 CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR
 PHOTOSENSOR.
 ALL TIME SWITCHES SHALL BE CAPABLE OF RETAINING
 PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER
 FOR A PERIOD OF AT LEAST 10 HOURS. FBC CE 405.2.4
  
 WALL PACKS TWO SHOWN NEED TO SUBMIT CUT SHEETS TYPE
 VSC-1 AND HOW THEY MOUNT
  
 VSF-1 NEED TO SHOW LOCATION OF ALL 12 ON PLANS DRAWINGS
 ONLY SHOW 2, PLUS SHOW HOW THEY MOUNT.
  
 WILL SUBMIT TO BUILDING WHEN ALL WIND LOADS AND CUT
 SHEETS ARE SUBMITTED.