Plan Review Notes
Plan Review Notes For Permit 18081074
Permit Number 18081074
Review Stop M
Sequence Number 1
Notes
Date Text
2018-09-18 17:20:001ST REVIEW FBC-2017 MECHANICAL
 REVISION #18081074
 MASTER #17110860
 9/18/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2.2, M2.3, & M2,4: THE SUPPLY AND RETURN DUCT
 DROPS FROM RTU-1-8B APPEAR TO MISLABLED AS DROPS FROM
 AHU 1-8A.
  
 2) THE REQUESTED WIND LOAD ENGINEERING FOR INSTALLING
 THE RTU'S IS INCOMPLETE. THERE ARE NO DETAILS SHOWING
 HOW THE CURBS WILL BE ATTACHED TO THE ROOF STRUCTURE.
 CONCERNING THE RTU ATTACHMENT TO THE CURBS, THE
 SUBMITTALS FROM ENGINEERS BUEROSSE P.E. AND BERNARDO
 P.E SHALL BE SIGNED AND SEALED PER SECTION 61G15-23.002
 FAC. IT WOULD BE HELPFUL TO INDICATE WHICH ENGINEERING
 APPLIES TO WHICH RTU- SECTION 107.2.1 WPB.
  
 3) PLEASE PROVIDE MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE HYDROGEN SENSORS-
 SECTION 404.1 FBC M.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  