Plan Review Notes
Plan Review Notes For Permit 18081074
Permit Number 18081074
Review Stop B
Sequence Number 1
Notes
Date Text
2018-09-27 14:10:48****CORRECTIONS****
 W.P.B. PERMIT: 18081074
 REVIEWED: SEPTEMBER 27, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
  
 [FBC 404.2.6]DOORS IN SERIES AND GATES IN SERIES.
 THE DISTANCE BETWEEN TWO HINGED OR PIVOTED DOORS IN
 SERIES AND GATES IN SERIES SHALL BE 48 INCHES (1220 MM)
 MINIMUM PLUS THE WIDTH OF DOORS OR GATES SWINGING INTO
 THE SPACE.
 ADJUST DOORS TO MEET ADA REQUIREMENTS AT VESTIBULE.
  