| 2018-09-13 09:53:23 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18081069 |
| | 9/13/18 |
| | |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE SUBMITTED PLANS FROM 2010 ARE NOT ACCEPTABLE FOR |
| | REVIEW. NEW PLANS DESIGNED IN ACCORDANCE WITH THE 2017 |
| | 6TH EDITION FLORIDA BUILDING CODES ARE REQUIRED PER FS |
| | 553.79(6) AND SECTION 107.2.1 WPB. THE SUBMITTED 2010 |
| | PLANS MAY BE MARKED "FOR REFERENCE ONLY" AND |
| | RESUBMITTED WITH THE NEW PLANS. |
| | |
| | 2) MINIMUM VENTILATION CALCULATIONS ARE REQUIRED FOR |
| | THE PROPOSED CHANGE OF OCCUPANCY. PLEASE SEE SECTION |
| | 1009.1 FBC EX, AND TABLE 403.3.1.1 FBC M. AND PROVIDE A |
| | SCHEDULE SHOWING THE REQUIRED AND PROVIDED CFMS OF |
| | OUTDOOR AIR FOR EACH ROOM OR SPACE. |
| | |
| | 3) PLEASE SEE SECTION C505.1 FBC EC AND NOTE THAT |
| | ENERGY CALCULATIONS AND A COMPLIANCE REPORT MAY BE |
| | REQUIRED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |