| 2018-08-29 16:45:57 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THE SUBMITTED PLANS DO NOT INCLUDE SUFFICIENT DETAIL |
| | TO COMPLETE A THOROUGH PLAN REVIEW. |
| | |
| | PER NFPA 1 |
| | 1.14 PLAN REVIEW. |
| | |
| | 1.14.2 THE APPLICANT SHALL BE RESPONSIBLE TO ENSURE |
| | THAT THE |
| | FOLLOWING CONDITIONS ARE MET: |
| | (1) THE CONSTRUCTION DOCUMENTS INCLUDE ALL OF THE FIRE |
| | PROTECTION |
| | REQUIREMENTS. |
| | |
| | THE PLAN SHEET PROVIDED ARE FROM AN OLD PLAN SET FROM |
| | 2010. |
| | |
| | PLEASE PROVIDE CURRENT PLAN SHEETS FOR A CERTIFIED |
| | DESIGN PROFESSIONAL. |
| | |
| | |
| | |
| | |
| | 2) THERE ARE NO INDICATIONS OF REVIEW OR COMPLIANCE |
| | WITH THE CURRENT FLORIDA LIFE SAFETY CODE. |
| | |
| | PER NFPA 101 THIS IS A NEW EDUCATIONAL OCCUPANCY AND |
| | SHALL COMPLY WITH THE 6TH EDITION OF THE FFPC. |
| | |
| | CHAPTER 1 ADMINISTRATION |
| | 1.3 APPLICATION. |
| | 1.3.1* NEW AND EXISTING BUILDINGS AND STRUCTURES. THE |
| | CODE SHALL |
| | APPLY TO BOTH NEW CONSTRUCTION AND EXISTING BUILDINGS |
| | AND EXISTING |
| | STRUCTURES. |
| | |
| | CHAPTER 14 NEW EDUCATIONAL OCCUPANCIES |
| | 14.1 GENERAL REQUIREMENTS. |
| | 14.1.1 APPLICATION. |
| | 14.1.1.1 THE REQUIREMENTS OF THIS CHAPTER SHALL APPLY |
| | TO NEW |
| | BUILDINGS OR PORTIONS THEREOF USED AS EDUCATIONAL |
| | OCCUPANCIES. |
| | |
| | PLEASE DESCRIBE IN DETAIL THE AGE AND GRADE LEVELS AS |
| | WELL AS THE HOURS OF OCCUPANCY. |
| | |
| | PLEASE PROVIDE AND DOCUMENT ALL THE APPLICABLE |
| | REQUIREMENTS OF THE OCCUPANCY CHAPTER. |
| | |
| | |
| | 3) THERE IS NO LIFE SAFETY PLAN FOR THIS OCCUPANCY. |
| | |
| | THIS IS A EDUCATIONAL OCCUPANCY AND A LIFE SAFETY PLAN |
| | IS REQUIRED. |
| | |
| | NFPA 101 |
| | |
| | 1.3.1.1 IF DEEMED NECESSARY BY AN AHJ FOR A COMPLETE, |
| | ACCURATE, AND |
| | THOROUGH FIRE SAFETY PLANS REVIEW OR INSPECTION, THE |
| | AHJ MAY REQUEST |
| | ASSISTANCE FROM THE BUILDING, ELECTRICAL, PLUMBING, |
| | MECHANICAL OR SIMILAR |
| | SPECIALTY INSPECTOR; HOWEVER, NOTHING IN THIS RULE |
| | GIVES AUTHORITY OR |
| | JURISDICTION TO ANY PERSON OTHER THAN A FIRE SAFETY |
| | INSPECTOR CERTIFIED |
| | UNDER SECTION 633.216, FLORIDA STATUTES, TO PERFORM |
| | FIRE SAFETY |
| | INSPECTIONS REQUIRED BY LAW, RULE, ORDINANCE, OR CODE. |
| | |
| | |
| | 4) THERE ARE NO INDICATIONS THE CORRIDORS MEET THE |
| | REQUIREMENTS FOR EDUCATIONAL OCCUPANCIES. |
| | |
| | NFPA 101 |
| | |
| | 14.3.6 CORRIDORS. CORRIDORS SHALL BE SEPARATED FROM |
| | OTHER PARTS OF |
| | THE STORY BY WALLS HAVING A 1-HOUR FIRE RESISTANCE |
| | RATING IN |
| | ACCORDANCE WITH SECTION 8.3, UNLESS OTHERWISE PERMITTED |
| | BY ONE OF |
| | THE FOLLOWING: |
| | (1) CORRIDOR PROTECTION SHALL NOT BE REQUIRED WHERE ALL |
| | SPACES |
| | NORMALLY SUBJECT TO STUDENT OCCUPANCY HAVE NOT LESS |
| | THAN ONE |
| | DOOR OPENING DIRECTLY TO THE OUTSIDE OR TO AN EXTERIOR |
| | EXIT |
| | ACCESS BALCONY OR CORRIDOR IN ACCORDANCE WITH 7.5.3. |
| | (2) THE FOLLOWING SHALL APPLY TO BUILDINGS PROTECTED |
| | THROUGHOUT |
| | BY AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM |
| | IN |
| | ACCORDANCE WITH SECTION 9.7: |
| | (A) CORRIDOR WALLS SHALL NOT BE REQUIRED TO BE RATED, |
| | PROVIDED THAT SUCH WALLS FORM SMOKE PARTITIONS IN |
| | ACCORDANCE WITH SECTION 8.4. |
| | (B) THE PROVISIONS OF 8.4.3.5 SHALL NOT APPLY TO |
| | NORMALLY |
| | OCCUPIED CLASSROOMS. |
| | (3) WHERE THE CORRIDOR CEILING IS AN ASSEMBLY HAVING A |
| | 1-HOUR |
| | FIRE RESISTANCE RATING WHERE TESTED AS A WALL, THE |
| | CORRIDOR |
| | WALLS SHALL BE PERMITTED TO TERMINATE AT THE CORRIDOR |
| | CEILING. |
| | (4) LAVATORIES SHALL NOT BE REQUIRED TO BE SEPARATED |
| | FROM |
| | CORRIDORS, PROVIDED THAT THEY ARE SEPARATED FROM ALL |
| | OTHER |
| | SPACES BY WALLS HAVING NOT LESS THAN A 1-HOUR FIRE |
| | RESISTANCE |
| | RATING IN ACCORDANCE WITH SECTION 8.3. |
| | (5) LAVATORIES SHALL NOT BE REQUIRED TO BE SEPARATED |
| | FROM |
| | CORRIDORS, PROVIDED THAT BOTH OF THE FOLLOWING CRITERIA |
| | ARE MET: |
| | (A) THE BUILDING IS PROTECTED THROUGHOUT BY AN |
| | APPROVED, |
| | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| | WITH SECTION 9.7. |
| | (B) THE WALLS SEPARATING THE LAVATORY FROM OTHER ROOMS |
| | FORM SMOKE PARTITIONS IN ACCORDANCE WITH SECTION 8.4. |
| | |
| | |
| | 5) A FIRE ALARM SHEET IS INDICATED; HOWEVER, PLEASE |
| | PROVIDE DETAILS THAT IT MEETS ALL THE REQUIRMENTS OF |
| | EDUCATIONAL OCCUPANCIES , INCLUDING BUT NOT LIMITED TO, |
| | |
| | 14.3.4.3 NOTIFICATION. |
| | 14.3.4.3.1 OCCUPANT NOTIFICATION. |
| | 14.3.4.3.1.1 OCCUPANT NOTIFICATION SHALL BE |
| | ACCOMPLISHED |
| | AUTOMATICALLY IN ACCORDANCE WITH 9.6.3. |
| | 14.3.4.3.1.2 THE OCCUPANT NOTIFICATION REQUIRED BY |
| | 14.3.4.3.1.1 |
| | SHALL UTILIZE AN EMERGENCY VOICE/ALARM COMMUNICATION |
| | SYSTEM IN |
| | ACCORDANCE WITH 9.6.3 WHERE THE BUILDING HAS AN |
| | OCCUPANT LOAD OF |
| | MORE THAN 100. |
| | 14.3.4.3.1.3 POSITIVE ALARM SEQUENCE SHALL BE PERMITTED |
| | IN |
| | ACCORDANCE WITH 9.6.3.4. |
| | 14.3.4.3.1.4 IN ACCORDANCE WITH 9.6.3.10.2 THE |
| | EMERGENCY |
| | VOICE/ALARM COMMUNICATION SYSTEM SHALL BE PERMITTED TO |
| | BE USED |
| | FOR OTHER EMERGENCY SIGNALING OR FOR CLASS CHANGES. |
| | 14.3.4.3.1.5 TO PREVENT STUDENTS FROM BEING RETURNED TO |
| | A BUILDING |
| | THAT IS BURNING, THE RECALL SIGNAL SHALL BE SEPARATE |
| | AND DISTINCT FROM |
| | ANY OTHER SIGNALS, AND SUCH SIGNAL SHALL BE PERMITTED |
| | TO BE GIVEN |
| | BY USE OF DISTINCTIVELY COLORED FLAGS OR BANNERS. |
| | 14.3.4.3.1.6 IF THE RECALL SIGNAL REQUIRED BY |
| | 14.3.4.3.1.5 IS ELECTRIC, |
| | THE PUSH BUTTONS OR OTHER CONTROLS SHALL BE KEPT UNDER |
| | LOCK, THE |
| | KEY FOR WHICH SHALL BE IN THE POSSESSION OF THE |
| | PRINCIPAL OR ANOTHER DESIGNATED PERSON IN ORDER TO |
| | PREVENT A RECALL AT A TIME |
| | WHEN THERE IS AN ACTUAL FIRE. |
| | 14.3.4.3.1.7 REGARDLESS OF THE METHOD OF RECALL SIGNAL, |
| | THE MEANS |
| | OF GIVING THE RECALL SIGNAL SHALL BE KEPT UNDER LOCK. |
| | |
| | |
| | |
| | 6) THERE IS NO INDICATIONS THAT WINDOWS COMPLY WITH THE |
| | FOLLOWING REQUIREMENT. |
| | |
| | 14.2.11 SPECIAL MEANS OF EGRESS FEATURES. |
| | 14.2.11.1* WINDOWS FOR RESCUE. |
| | 14.2.11.1.1 EVERY ROOM OR SPACE GREATER THAN 250 FT2 |
| | (23.2 M2) |
| | AND USED FOR CLASSROOM OR OTHER EDUCATIONAL PURPOSES OR |
| | NORMALLY |
| | SUBJECT TO STUDENT OCCUPANCY SHALL HAVE NOT LESS THAN |
| | ONE OUTSIDE |
| | WINDOW FOR EMERGENCY RESCUE THAT COMPLIES WITH ALL OF |
| | THE |
| | FOLLOWING, UNLESS OTHERWISE PERMITTED BY 14.2.11.1.2: |
| | (1) SUCH WINDOWS SHALL BE OPENABLE FROM THE INSIDE |
| | WITHOUT THE |
| | USE OF TOOLS AND SHALL PROVIDE A CLEAR OPENING OF NOT |
| | LESS THAN |
| | 20 IN. (510 MM) IN WIDTH, 24 IN. (610 MM) IN HEIGHT, |
| | AND 5.7 |
| | FT2 (0.5 M2) IN AREA. |
| | (2) THE BOTTOM OF THE OPENING SHALL BE NOT MORE THAN 44 |
| | IN. |
| | (1120 MM) ABOVE THE FLOOR, AND ANY LATCHING DEVICE |
| | SHALL BE |
| | CAPABLE OF BEING OPERATED FROM NOT MORE THAN 54 IN. |
| | (1370 |
| | MM) ABOVE THE FINISHED FLOOR. |
| | (3) THE CLEAR OPENING SHALL ALLOW A RECTANGULAR SOLID, |
| | WITH A |
| | WIDTH AND HEIGHT THAT PROVIDES NOT LESS THAN THE |
| | REQUIRED 5.7 |
| | FT2 (0.5 M2) OPENING AND A DEPTH OF NOT LESS THAN 20 |
| | IN. (510 |
| | MM), TO PASS FULLY THROUGH THE OPENING. |
| | (4) SUCH WINDOWS SHALL BE ACCESSIBLE BY THE FIRE |
| | DEPARTMENT AND |
| | SHALL OPEN INTO AN AREA HAVING ACCESS TO A PUBLIC WAY. |
| | 14.2.11.1.2 THE REQUIREMENTS OF 14.2.11.1.1 SHALL NOT |
| | APPLY TO ANY |
| | OF THE FOLLOWING: |
| | (1) BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED, |
| | SUPERVISED |
| | AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION |
| | 9.7 |
| | (2) WHERE THE ROOM OR SPACE HAS A DOOR LEADING DIRECTLY |
| | TO AN |
| | EXIT OR DIRECTLY TO THE OUTSIDE OF THE BUILDING |
| | (3) RESERVED |
| | (4) ROOMS LOCATED FOUR OR MORE STORIES ABOVE THE |
| | FINISHED |
| | GROUND LEVEL |
| | |
| | PLEASE PROVIDE DETAILS OR JUSTIFY. |
| | |
| | |
| | |
| | |
| | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |