| 2018-09-22 12:42:21 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. FBC EB 301.1, THE ALTERATION, CHANGE OF OCCUPANCY IS |
| | TO COMPLY WITH ONE OF THE METHODS LISTED IN 301.1.1 |
| | THROUGH 301.1.3 AS SELECTED BY APPLICANT. REVISE PLAN |
| | TO SPECIFY; MOST COMMON IS WORK AREA COMPLIANCE METHOD. |
| | IF THAT IS ELECTED, REVISE PLAN TO INCLUDE CHAPTER 10 |
| | CHANGE OF OCCUPANCY AND LEVEL 1 OR LEVEL 2 ALTERATION |
| | AS APPLICABLE. |
| | |
| | SINCE THE FLOOR PLAN IS NOT LEGIBLE, WORK PROPOSED IS |
| | NOT CLEAR. NOTHING IS NOTED AS "EXISTING" OR "PROPOSED |
| | NEW". THE LATEST PERMIT PLANS ARE HELPFUL TO DOCUMENT |
| | EXISTING CONDITIONS BUT THE NEW PLAN NEEDS TO BE CLEAR |
| | AS TO WORK PROPOSED AND EXISTING TO REMAIN. |
| | |
| | 2. FBC 107, REVISE PLAN TO INCLUDE THE PRINTED NAME AND |
| | SIGNATURE OF INDIVIDUAL TAKING RESPONSIBILITY FOR THE |
| | DESIGN/INFORMATION. |
| | |
| | 3. FBC 107, PLAN IS NOT LEGIBLE DUE TO THE GREY OVER |
| | THE FLOOR PLAN. EITHER REMOVE THE GREY OR MAKE THE PLAN |
| | LEGIBLE IN ANOTHER MANNER. ALL ROOM DESIGNATIONS, |
| | SQUARE FOOT AREA, OTHER INFORMATION IS TO BE EASILY |
| | READABLE AND ALSO READABLE ON PAPER AND ALSO AFTER |
| | SCANNING. |
| | |
| | 4. FBC 107, DECLARE AN OCCUPANT LOAD. PLAN STATES THAT |
| | THE SCHOOL IS LIMITED TO 100 STUDENTS. REVISE PLAN TO |
| | CLEARLY NOTE DESIGN OCCUPANT LOAD. NUMBER OF STAFF |
| | SHOULD BE INCLUDED. |
| | |
| | 5. FBC 107, REVISE PLAN TO STATE EXISTING OCCUPANCY |
| | (BUSINESS), PROPOSED OCCUPANCY (EDUCATION). |
| | |
| | 6. A NOTE STATES THAT THE REAR DOOR HAS PANIC BARS. SEE |
| | FBC EB 1005.1, FBC EB 1012.4.1, FBC B 1010.1.10. |
| | |
| | 7. REVISE PLAN TO SHOW SQUARE FOOT AREA FOR EACH ROOM, |
| | OCCUPANT LOAD FOR EACH ROOM, FBC B 1010.1.10. SEE FBC B |
| | TABLE 1004.1.2, USE 20 SF NET PER PERSON. ALTHOUGH A |
| | REDUCED OCCUPANT LOAD FOR DETERMINING PLUMBING FIXTURES |
| | WAS REQUIRED, MEANS OF EGRESS TO COMPLY WITH THE TABLE. |
| | IF ANY ROOM HAS AN OCCUPANT LOAD OVER 50, A PANIC BAR |
| | IS REQUIRED AND SHOULD BE NOTED ON THE PLAN. |
| | |
| | 8. FBC EB TABLE 1012.5, SHOW COMPLIANCE FOR BUIDING |
| | HEIGHT AND AREA AS THIS IS A CHANGE TO A HIGHER HAZARD. |
| | |
| | 9. REVISE PLAN TO INCLUDE GOVERNING CODE (FLORIDA |
| | BUILDING CODE 6TH EDITION). |
| | |
| | |
| | |
| | |
| | |