2018-11-29 17:11:58REVISION THIRD BUILDING REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014) AND CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 1-ENGINEERED PLANS SHOW THE METAL SCREENING ATTACHED TO
 THE A/C UNIT. TYPICALLY, A/C UNITS ARE NOT DESIGNED TO
 RESIST ADDITIONAL WIND LOADS. PROVIDE A/C MANUFACTURES
 SPECS SHOWING THAT THE UNIT IS DESIGNED FOR THIS
 ADDITIONAL LOAD OR PROVIDE COMPLETE ENGINEERING
 ANALYSIS SHOWING THAT THE EXISTING A/C UNIT WILL RESIST
 THE ADDITIONAL LOAD. SEC. 1609 FBC AND SEC. 107.2.1.2
 CITY AMENDMENTS.
  
 RESPONSE:
 SPINNAKER INDUSTRIES SLIDING LOUVERED PANEL
 ARCHITECTURAL SCREENING SPECIFICATION SUBMITTED
 SPECIFIES "THE SCREENING WILL BE SHIPPED "KOCKED-DOWN"
 AS AN ASSEMBLY KIT WHICH WILL MOUNT DIRECTLY TO THE
 MECHANICAL EQUIPMENT (NO ROOF-TOP PENETRATION WILL BE
 REQUIRED, OR ALLOWED)". NEED TO PROVIDE ENGINEERING
 ANALYSIS OR A/C MANUFACTUER SPECIFICATIONS SHOWNG THAT
 THE A/C WILL RESIST THE ADDTIONAL LOADS. OR ENGINEER OF
 RECORD PROVIDE COMPLETE DETAISLA ND SPECIFICATIONS FOR
 SCREENING TO BE ATTACHED TO THE A/C CURB NOT THE A/C
 UNIT. SEC. 1609 FBC AND SEC. 107.2.1.2 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 2- PROVIDE PLAN SHOWING THE LOCATION OF THE PROPOSED
 SCREENS. SEC. 1107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 SCOPE OF WORK SHOWN ON DRAWINGS FROM JACOBS SUBMITTED
 VIA E-MAI ON 11/27/18 IS NOT CLEAR. EQUIPMENT SHOWN ON
 FLOOR PLAN ON SHEET SK-1 AND SK-2 DOESN'T MATCH. NOT
 CLEAR IF INSTALLING SCREEN POSTS OR NOT. AND LOCATIOIN
 OF POST DON'T MATCH . CLARIFY IS USIING SPINNAKER
 INSUATRIES OR CITYSCAPES. COORDIANTE AS REQUIRED. SEC.
 107.2.1 CITY AMENDMENTS.
  
 3- RE-SUBMIT COMPLETE COORDINATED PACKAGE FOR REVIEW.
 NOTE: MECHANICAL PLAN REVIEWER WILL NEED TO REVIEW
 PLANS FOR COMPLIANCE WITH ACCESS FOR SERVICE AND
 REPLACEMENT. PROVIDE THIS INFORAMTION FOR MECHANICAL
 REVIEW TO AVODI/CONFLICTS DELAYS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected].


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved