2018-09-26 13:15:22REVISION SECOND BUILDING REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014) AND CITY AMENDMENTS.
  
 1-ENGINEERED PLANS SHOW THE METAL SCREENING ATTACHED TO
 THE A/C UNIT. TYPICALLY, A/C UNITS ARE NOT DESIGNED TO
 RESIST ADDITIONAL WIND LOADS. PROVIDE A/C MANUFACTURES
 SPECS SHOWING THAT THE UNIT IS DESIGNED FOR THIS
 ADDITIONAL LOAD OR PROVIDE COMPLETE ENGINEERING
 ANALYSIS SHOWING THAT THE EXISTING A/C UNIT WILL RESIST
 THE ADDITIONAL LOAD. SEC. 1609 FBC AND SEC. 107.2.1.2
 CITY AMENDMENTS.
  
 2- PROVIDE PLAN SHOWING THE LOCATION OF THE PROPOSED
 SCREENS. SEC. 1107.2.1 CITY AMENDMENTS.
  
 3- ADDRESS SHOWN IN THE TITLE BLOCK DOESN'T MATCH
 ADDRESS OF BUILDING UNDER MASTER NUMBER 17100607. THE
 ADDRESS SHOWN ON APPROVED PLANS IS 851 VILLAGE BLVD
 #502. . REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
  
  