| 2018-09-26 13:15:22 | REVISION SECOND BUILDING REVIEW CHECKLIST. | | | CODE: FBC 5TH EDITION (2014) AND CITY AMENDMENTS. | | | | | | 1-ENGINEERED PLANS SHOW THE METAL SCREENING ATTACHED TO | | | THE A/C UNIT. TYPICALLY, A/C UNITS ARE NOT DESIGNED TO | | | RESIST ADDITIONAL WIND LOADS. PROVIDE A/C MANUFACTURES | | | SPECS SHOWING THAT THE UNIT IS DESIGNED FOR THIS | | | ADDITIONAL LOAD OR PROVIDE COMPLETE ENGINEERING | | | ANALYSIS SHOWING THAT THE EXISTING A/C UNIT WILL RESIST | | | THE ADDITIONAL LOAD. SEC. 1609 FBC AND SEC. 107.2.1.2 | | | CITY AMENDMENTS. | | | | | | 2- PROVIDE PLAN SHOWING THE LOCATION OF THE PROPOSED | | | SCREENS. SEC. 1107.2.1 CITY AMENDMENTS. | | | | | | 3- ADDRESS SHOWN IN THE TITLE BLOCK DOESN'T MATCH | | | ADDRESS OF BUILDING UNDER MASTER NUMBER 17100607. THE | | | ADDRESS SHOWN ON APPROVED PLANS IS 851 VILLAGE BLVD | | | #502. . REVISE AS REQUIRED. SEC. 107.2.1 CITY | | | AMENDMENTS. | | | | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | |
|