| 2018-12-21 07:32:58 | 2ND REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PREVIOUS MED GAS COMMENTS: 2ND REQUEST |
| | 1. NOT COMPLIED: PROVIDE A SCHEDULE FOR ALL MED GAS |
| | EQUIPMENT. PER WPB AMEND TO FBC 107.2.1 |
| | 2. NOT COMPLIED: PROVIDE MANUFACTURE SPECIFICATIONS AND |
| | INSTALLATION GUIDES FOR ALL MED GAS EQUIPMENT INCLUDING |
| | THE TANKS AND VALVES. PER WPB AMEND TO FBC 107.2.1 |
| | 3. COMPLIED |
| | 4. NOT COMPLIED: SHT. P-903 ON THE ISOMETRIC WHEN A |
| | PIPE IS CROSSING ANOTHER PIPE IT SHOULD HAVE A GAP AS |
| | THEY LOOK NOW A NUMBER OF PIPES APPEAR TO BE CONNECTED |
| | TOGETHER IT IS DIFFICULT TO DETERMINE WHICH SYSTEMS IS |
| | WHICH PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | ISOMETRIC IS STILL TO CONGESTED TO READ PLEASE EXPAND. |
| | 5. NOT COMPLIED: PLEASE PROVIDE DETAIL OF THE STRAPPING |
| | OF THE MED GAS STORAGE TANKS. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | 6. NOT COMPLIED: A SEPARATE PERMIT IS REQUIRED FOR MED |
| | GAS, ALONG WITH THE APPLICATION PROOF OF MED GAS |
| | CERTIFICATION FOR THE CONTRACTOR AND INSTALLER IS |
| | REQUIRED. PER FAC 61G4-15.031(1) (4) (A) (B) PLEASE |
| | PLACE NOTE ON PLAN. |
| | 7. COMPLIED |
| | 8. COMPLIED |
| | NEW COMMENTS: |
| | 1. PLEASE PROVIDE DETAILS FOR THE MED GAS ZONE VALVES 5 |
| | PORTS AND 2 PORTS. PER WPB AMEND TO FBC 107.2.1 |
| | 2. THE VACUUM EXHAUST PIPE ON SHEET P-802 DETAIL #4 |
| | SHOWS THE PIPING AT 2" THE NOTE STATES IT 1-1/2" SHEET |
| | P-205 KEY NOTE #2 STATES IT AT STATES IT AT 3" PLEASE |
| | CHECK ALL NOTES DETAILS AND ISOMETRIC AND SIZE THE |
| | SYSTEM THE SAME PER THE MANUFACTURE SPECIFICATIONS. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | 3. SHEET P-903 THE MED GAS ISOMETRIC IS SHOWING THE |
| | VACUUM EXHAUST PIPING LABELED AS MV PRESSURE RELIEF |
| | VENT IT SHALL BE LABELED TO MATCH THE REST OF THE PLAN |
| | AND THE TEXT IN THE CODE AS VACUUM EXHAUST PIPING. PER |
| | NFPA 99 |
| | 4. PLEASE STATE ON THE PLAN WHAT CATEGORY THE MED GAS |
| | SYSTEM IS DESIGNED TO BE. PER NFPA 99 CHAPTER 4 |
| | 5. THE LIFE SAFETY SHEETS SHOWS A MED GAS STORAGE |
| | SCHEDULE PLEASE INCLUDE THIS ON THE MED GAS PLAN |
| | SHEETS. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |